Technical DataΒΆ
The System Data of AC500-eCo apply System Data AC500-eCo
Only additional details are therefore documented below.
Parameter | Value | |
---|---|---|
Process voltage UP | ||
Connections | Terminals 17 and 19 for UP (+24 V DC); terminals 18 and 20 for ZP (0 V) | |
Rated value | 24 V DC | |
Current consumption via UP terminal | 10 mA + 0.1 A per output (max.) | |
Max. ripple | 5 % | |
Inrush current | 0.000001 A:sup:2s | |
Protection against reversed voltage | Yes | |
Protection fuse on UP | Recommended; the outputs must be protected by an 1 A fast fuse | |
Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/bus module | Ca. 10 mA | |
Galvanic isolation | Yes, between the input/output group and the rest of the module | |
Isolated groups | 1 group for 16 channels | |
Surge voltage (max.) | 35 V DC for 0.5 s | |
Max. power dissipation within the module | On request | |
Input data length | 2 bytes | |
Output data length | 2 bytes | |
Weight | Ca. 115 g | |
Mounting position | Horizontal or vertical | |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
No effects of multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an external fuse.