Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Parameter Value
Interface Serial interface
Transmission rate 2.4 kBit/s to 19.2 kBit/s
Protocol RCOM/RCOM+
Interface connector MC 0.5/9-G-2.5, 9-pin, male
Processor PowerPC
Usable CPUs PM57x, PM58x, PM59x PM57x (-y), PM58x (-y) and PM59x (-y)
Usable terminal bases All TB5xx TB51x-TB54x
Ambient temperature

see:

System data AC500 System Data AC500

System Data AC500 XC System Data AC500-XC

Communication module bus Dual-port memory, 8 kByte
Internal power supply Through the communication module bus of the terminal base
Current consumption from 24 V DC power supply at the terminal base of the CPU Typ. 80 mA
Internal RAM memory 256 kByte
External RAM memory -
External flash memory 512 kByte (firmware)
State display PWR, RDY, RUN, STA, ERR
Weight Ca. 150 g
Technical Data of the Interfaces
Parameter Value
Serial interface standard EIA RS-232 or EIA RS-485
Interface connector Pluggable 9-pin terminal block
Potential separation Yes, from the CPU, 500 V DC
Serial interface parameters Protocol interface configurable via PLC configuration. Preset configuration for debugging the terminal interface.
Modes of operation Data exchange
Protocols supported RCOM/RCOM+

The pin assignment of the serial interfaces RCOM and OPERATOR is identical to the serial interface COM1 of the processor modules PM57x, PM58x and PM59x.