Technical Data of the Digital \ Inputs

Parameter Value
Number of channels per module 8
Distribution of the channels into groups 1 group of 8 channels
Terminals of the channels DI0 to DI7 Terminals 3.0 to 3.7
Reference potential for all inputs Terminals 2.9 … 4.9 (negative pole of the supply voltage, signal name ZP)
Indication of the input signals 1 yellow LED per channel, the LED is ON when the input signal is high (signal 1)
Input type (according EN 61131-2) Type 1
Input delay (0->1 or 1->0) Typ. 0.1 ms, configurable from 0.1…32 ms
Input signal voltage 24 VDC
Signal 0 -3 V…+5 V
Undefined signal > +5 V…< +15 V
Signal 1 +15 V…+30 V
Ripple with signal 0 Within -3 V…+5 V
Ripple with signal 1 Within +15 V…+30 V
Input current per channel  
Input voltage +24 V Typ. 5 mA
Input voltage +5 V > 1 mA
Input voltage +15 V > 2 mA
Input voltage +30 V < 8 mA
Max. cable length  
Shielded 1000 m
Unshielded 600 m