Technical Data of the Module

Process supply voltages UP  
  Rated value 24 VDC
  Max. load for the terminals 10 A
  Protection against reversed voltage Yes
  Rated protection fuse on UP 10 A fast
  Inrush current from UP (at power up) On request
  Current consumption via UP (normal operation) 0.15 A
  Connections

Terminals 1.0, 2.0 and 3.0 for +24 V (UP)

Terminals 1.1, 2.1 and 3.1 for 0 V (ZP)

Input data length 0 … 36 bytes
Output data length 0 … 36 bytes
Max. power dissipation within the module 5 W
Setting of the IO Device identifier With 2 rotary switches at the front side of the module
Operation and error displays 18 LEDs (total)
Weight (without Terminal Unit) ca. 125 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.
Electrical isolation ETHERNET interface against the rest of the module, each serial and CAN port against each other and the rest of the module
Diagnosis See Diagnosis CI506-PNIO

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.

No effects of multiple overloads

No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an internal smart high-side switch.

Bus connection 2 x RJ45
Switch Integrated
Technology Hilscher netX100
Transfer rate 10/100 MBit/s (full-duplex)
Transfer method According to ETHERNET II, IEE802.3
Expandability Max. 10 S500 I/O modules
Adjusting elements 2 rotary switches for generation of an explicit name
Supported protocols

RTC - real-time cyclic protocol, class 1 *

RTA - real-time acyclic protocol

DCP - discovery and configuration protocol

CL-RPC - connectionless remote procedure Call

LLDP - link layer discovery protocol

Acyclic services

PNIO read / write sequence (max. 1024 bytes per telegram)

Process-Alarm service

Supported alarm types Process Alarm, Diagnostic Alarm, Return of SubModule, Plug Alarm, Pull Alarm
Min. bus cycle 1 ms
Conformance Class CC A
Protective functions (according to IEC 61131-3)

Protected against:

- short circuit

- reverse supply

- overvoltage

- reverse polarity

Electrical isolation from the rest of the module

* Priorization with the aid of VLAN-ID including priority level