Technical Data of the Module¶
Process supply voltages UP | ||
Rated value | 24 VDC | |
Max. load for the terminals | 10 A | |
Protection against reversed voltage | Yes | |
Rated protection fuse on UP | 10 A fast | |
Inrush current from UP (at power up) | On request | |
Current consumption via UP (normal operation) | 0.15 A | |
Connections | Terminals 1.0, 2.0 and 3.0 for +24 V (UP) Terminals 1.1, 2.1 and 3.1 for 0 V (ZP) |
|
Input data length | 0 … 36 bytes | |
Output data length | 0 … 36 bytes | |
Max. power dissipation within the module | 5 W | |
Setting of the IO Device identifier | With 2 rotary switches at the front side of the module | |
Operation and error displays | 18 LEDs (total) | |
Weight (without Terminal Unit) | ca. 125 g | |
Mounting position | Horizontal or vertical | |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Electrical isolation | ETHERNET interface against the rest of the module, each serial and CAN port against each other and the rest of the module |
Diagnosis | See Diagnosis CI506-PNIO |
Attention
:strong:Attention:
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.
No effects of multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an internal smart high-side switch.
Bus connection | 2 x RJ45 |
Switch | Integrated |
Technology | Hilscher netX100 |
Transfer rate | 10/100 MBit/s (full-duplex) |
Transfer method | According to ETHERNET II, IEE802.3 |
Expandability | Max. 10 S500 I/O modules |
Adjusting elements | 2 rotary switches for generation of an explicit name |
Supported protocols | RTC - real-time cyclic protocol, class 1 * RTA - real-time acyclic protocol DCP - discovery and configuration protocol CL-RPC - connectionless remote procedure Call LLDP - link layer discovery protocol |
Acyclic services | PNIO read / write sequence (max. 1024 bytes per telegram) Process-Alarm service |
Supported alarm types | Process Alarm, Diagnostic Alarm, Return of SubModule, Plug Alarm, Pull Alarm |
Min. bus cycle | 1 ms |
Conformance Class | CC A |
Protective functions (according to IEC 61131-3) | Protected against: - short circuit - reverse supply - overvoltage - reverse polarity Electrical isolation from the rest of the module |
* Priorization with the aid of VLAN-ID including priority level