Parameterization

Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is performed by Control Builder Plus/ Automation_Builder software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module: Module slot address: Y = 1…10

Name Value Internal value Internal value, type Default Min. Max.

EDS

Slot/Index

Module ID Internal

1205

1)

Word

1205

0x04B5

0 65535 0x0Y01

Ignore module

2)

No

Yes

0

1

Byte

No

0x00

    not for FBP
Parameter length Internal 4 Byte

4-CPU

4-FBP

0 255 0x0Y02
Check supply

Off

on

0

1

Byte

On

0x01

0 1 0x0Y03
Input delay

20 ms

100 ms

0

1

Byte

20 ms

0x00

0 1 0x0Y04
Behaviour of outputs at communication errors

Off

Last value

Substitute value

0

1+(n*5)

2+(n*5),

n <= 2

Byte

Off

0x00

0 2 0x0Y05

Substitute value at outputs

Bit 3 = Output 3

Bit 0 = Output 0

0…15

0…

0x0f

Byte

0

0x00

0 15 0x0Y06

1) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1

2) Not with FBP

GSD file:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const

  1. =

7

0x04, 0xb6, 0x04, \

0x01, 0x00, 0x00, 0x00;