Technical Data of the Module

Process supply voltages UP/UP3  
  Rated value 24 VDC (for inputs and outputs)
  Max. load for the terminals 10 A
  Protection against reversed voltage Yes
  Rated protection fuse on UP/UP3 10 A fast
  Electrical isolation PROFIBUS interface against the rest of the module
  Inrush current from UP (at power up) On request
  Current consumption via UP (normal operation) 0.2 A
  Current consumption via UP3 0.06 A + 0.5 A max. per output
  Connections

Terminals 2.8 and 3.8 for +24 V (UP)

Terminal 4.8 for +24 V (UP3)

Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)

Max. power dissipation within the module 6 W
Number of digital inputs 8
Number of digital outputs 8
Number of analog inputs 4
Number of analog outputs 2
Reference potential for all digital inputs and outputs Minus pole of the supply voltage, signal name ZP
Setting of the PROFIBUS DP identifier With 2 rotary switches at the front side of the module
Diagnose See Diagnosis CI541-DP
Operation and error displays 32 LEDs (totally)
Weight (without Terminal Unit) Ca. 125 g
Mounting position

Horizontal

Or vertical with derating (output load reduced to 50 % at 40 °C per group)

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.

No effects of multiple overloads

No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an internal smart high-side switch.