Comparison CI581 and CI582

CI581/CI582: Technical data

Parameter Value
Interface CAN
Protocol CANOPEN
Power supply From the process supply voltage UP
Supply of the electronic circuitry of the decentralized communication interface modules attached Through the expansion bus interface (I/O bus)
Rotary switches For setting the CANOPEN Node ID for configuration purposes (00h to FFh)
LED displays For system displays, signal states, errors and power supply
External supply voltage Via terminals ZP, UP and UP3 (process supply voltage 24 VDC)
Transmission rates 10 / 20 / 50 / 125 / 250 / 500 / 800 kbit/s 1 Mbit/s Auto baudrate detection is supported
Bus connection Depending on used terminal unit TU510: 9-pin D-sub connector TU518: 10-pin terminal block
Processor Hilscher netX100
Expandability Max. 10 S500 I/O modules
State display Module state: PWR/RUN, CN-RUN, CN-ERR, E-ERR, I/O bus
Adjusting elements 2 rotary switches for generation of the node address
Ambient temperature

System data AC500 System Data AC500

System data AC500 XC System Data AC500-XC

Current consumption UP: 0.2 A UP3: 0.06 A + 0.5 A max. per output
Weight (without terminal unit) Ca. 125g
Process supply voltages UP/UP3  
  Rated value 24 VDC (for inputs and outputs)
  Max. load for the terminals 10 A
  Protection against reversed voltage Yes
  Rated protection fuse on UP/UP3 10 A fast
  Galvanic isolation CANOPEN interface against the rest of the module
  Inrush current from UP (at power up) On request
  Current consumption via UP (normal operation) 0.2 A
  Current consumption via UP3 0.06 A + 0.5 A max. per output
  Connections

Terminals 2.8 and 3.8 for +24 V (UP)

Terminal 4.8 for +24 V (UP3)

Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)

Max. power dissipation within the module 6 W
Reference potential for all digital inputs and outputs Minus pole of the supply voltage, signal name ZP
Setting of the CANOPEN Node ID identifier With 2 rotary switches at the front side of the module
Mounting position

Horizontal

Or vertical with derating (output load reduced to 50 % at 40 °C per group)

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.
Effect of incorrect input terminal connection Wrong or no signal detected, no damage up to 35V
Required terminal unit TU509, TU510, TU517 or TU518 TU509 and TU510 for Communication Interface Modules TU517 and TU518 for Communication Interface Modules

Note

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.

The difference of those devices can be found in their input and output characteristics.

CI581-CN: Input/Output Characteristics

Parameter Value
Inputs and outputs

8 digital inputs (24 VDC; delay time configurable via software)

8 digital transistor outputs (24 VDC, 0.5 A max.)

4 analog inputs, configurable as:

  • -10…+10 V
  • 0…+10 V
  • -10…+10 V (differential voltage)
  • 0…20 mA
  • 4…20 mA
  • Pt100 , Pt1000, Ni1000 (for each 2-wire and 3-wire)
  • 24 V digital input function

2 analog outputs, configurable as:

  • -10…+10 V
  • 0…20 mA
  • 4…20 mA
Resolution of the analog channels 12 bits
Fast counter Integrated, configurable operating modes

CI582-CN: Input/Output Characteristics

Parameter Value
Inputs and outputs

8 digital inputs (24 VDC)

8 digital transistor outputs (24 VDC, 0.5 A max.)

8 configurable digital inputs/outputs (24 VDC, 0.5 A max.)