Connection of resistance thermometers in 3-wire configuration¶
When resistance thermometers (Pt100, Pt1000, Ni1000, Cu50) are used, a constant current must flow through them to build the necessary voltage drop for the evaluation. For this, the module AI531 provides a constant current source which is multiplexed over the 4 analog channels.
Connection example
The following measuring ranges can be configured AI531 - Analog Input Module AI531 - Analog Input Module (see also
Pt100 | -50 °C … +70 °C / +400 °C; -200 °C … +850 °C | 1 channel used |
Pt1000 | -50 °C … +400 °C | 1 channel used |
Ni1000 | -50 °C … +150 °C | 1 channel used |
Cu50 | -50 °C … +200 °C (1.426); -200 °C … +200 °C (1.428) | 1 channel used |
For a description of the function of the LEDs, please refer to Diagnosis and displays / displays AI531 - Analog Input Module.
The module linearizes the resistance thermometer characteristics. In order to keep measuring errors as small as possible, it is necessary by all means to have all the involved conductors in the same cable. All the conductors must have the same cross section.
In order to avoid error messages from unused analog input channels, it is useful to configure them as “unused”.