Technical DataΒΆ

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Parameter Value
Protocol CANOPEN slave
Technology Hilscher netX100
Usable CPUs PM57x, PM58x, PM59x PM57x (-y), PM58x (-y) and PM59x (-y)
Usable terminal bases All TB5xx TB51x-TB54x
Bus connection Pluggable connector COMBICON, 2x5-pin
Internal power supply Via the communication module Interface of the terminal base
Transfer rate 10 kBit/s to 1 MBit/s
Transfer method According to CAN standard
Bus length (segment length max.) According to table: Maximum cable length within a CANOPEN field bus
Indicators 5 LEDs
Current consumption from 24 V DC power supply at the terminal base of the CPU Typ. 65 mA
Weight Ca. 150 g
Ambient temperature

see:

System data AC500 System Data AC500

System Data AC500-XC System Data AC500-XC

Adjusting elements None
Quantity of input and output data per I/O device Max. 512 byte (respectively for input and output)
Supported protocol services

NMT slave

PDO

SDO server

Heartbeat

Nodeguard

Min. bus cycle 1 ms