Connection of resistance thermometers in 2-wire configuration¶
When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow through them to build the necessary voltage drop for the evaluation. For this, the I/O module provides a constant current source which is multiplexed over the 8 analog channels.
Connection example
Pt100 | -50 °C…+70 °C | 2-wire configuration, one channel used |
Pt100 | -50 °C…+400 °C | 2-wire configuration, one channel used |
Pt1000 | -50 °C…+400 °C | 2-wire configuration, one channel used |
Ni1000 | -50 °C…+150 °C | 2-wire configuration, one channel used |
The I/O module performs a linearization of the resistance characteristic.
In order to avoid error messages from unused analog input channels, it is useful to configure them as “unused”.