Channel \ Parameters for the Analog Outputs (2x)

Name Value Internal value Internal value, type Default
Output 0, Channel configuration Table Operating modes of the analog outputs CI521-MODTCP Table Operating modes of the analog outputs CI521-MODTCP BYTE 0
Output 0, Check channel Table Channel monitoring CI521-MODTCP Table Channel monitoring CI521-MODTCP BYTE 0
Output 0, Substitute value Table Substitute value CI521-MODTCP Table Substitute value CI521-MODTCP WORD 0
Output 1, Channel configuration Table Operating modes of the analog outputs CI521-MODTCP Table Operating modes of the analog outputs CI521-MODTCP BYTE 0
Output 1, Check channel Table Channel monitoring CI521-MODTCP Table Channel monitoring CI521-MODTCP BYTE 0
Output 1, Substitute value Table Substitute value CI521-MODTCP Table Substitute value CI521-MODTCP WORD 0
Channel Configuration
Internal value Operating modes of the analog outputs, individually configurable
0 (default) Not used
128 -10 V…+10 V
129 0…20 mA
130 4…20 mA
Channel Monitoring
Internal value Check channel
0 Plausib(ility), cut wire, short circuit
3 None
Substitute Value
Intended behaviour of output channel when the control system stops Required setting of the module parameter “Behaviour of outputs in case of a communication error” Required setting of the channel parameter “Substitute value”
Output OFF Off 0
Last value infinite Last value 0
Last value for 5 s and then turn off Last value 5 sec 0
Last value for 10 s and then turn off Last value 10 sec 0
Substitute value infinite Substitute value Depending on configuration
Substitute value for 5 s and then turn off Substitute value 5 sec Depending on configuration
Substitute value for 10 s and then turn off Substitute value 10 sec Depending on configuration