FunctionalityΒΆ

Parameter Value
Interface ETHERNET
Protocol MODBUS TCP
Power supply From the process supply voltage UP
Supply of the electronic circuitry of the I/O expansion modules attached Through the expansion bus interface (I/O bus)
Rotary switches for setting the last BYTE of the IP (00h to FFh)
Analog inputs 4 (configurable via software)
Analog outputs 2 (configurable via software)
Digital inputs 8 (24 VDC; delay time configurable via software)
Digital outputs 8 (24 VDC, 0.5 A max.)
LED displays For system displays, signal states, errors and power supply
External supply voltage Via terminals ZP, UP and UP3 (process supply voltage 24 VDC)
Required terminal unit TU507 or TU508 TU507-ETH and TU508-ETH for ETHERNET Communication Interface Modules