Parameters of the Module¶
Name | Value | Internal value | Internal value, type | Default |
---|---|---|---|---|
Module ID 1) | Internal | 7400 | WORD | 7000 |
Ignore Module | Internal | 0 | BYTE | 0 |
Parameter length | Internal | 63 | BYTE | 63 |
Error LED / Failsafe function see table Error LED / Failsafe function CI521-MODTCP | On | 0 | BYTE | 0 |
Off by E4 | 1 | |||
Off by E3 | 3 | |||
On + failsafe | 16 | |||
Off by E4 + failsafe | 17 | |||
Off by E3 + failsafe | 19 | |||
Master IP for Write restriction 4) | No master IP Master IP |
0,0,0,0 W,X,y,z | ARRAY[0..3] OF BYTE | 0,0,0,0 |
Master IP for Write restriction 4) | No master IP Master IP |
0,0,0,0 W,X,y,z | ARRAY[0..3] OF BYTE | 0,0,0,0 |
Master IP for Write restriction 4) | No master IP Master IP |
0,0,0,0 W,X,y,z | ARRAY[0..3] OF BYTE | 0,0,0,0 |
Master IP for Write restriction 4) | No master IP Master IP |
0,0,0,0 W,X,y,z | ARRAY[0..3] OF BYTE | 0,0,0,0 |
Master IP for Write restriction 4) | No master IP Master IP |
0,0,0,0 W,X,y,z | ARRAY[0..3] OF BYTE | 0,0,0,0 |
Master IP for Write restriction 4) | No master IP Master IP |
0,0,0,0 W,X,y,z | ARRAY[0..3] OF BYTE | 0,0,0,0 |
Master IP for Write restriction 4) | No master IP Master IP |
0,0,0,0 W,X,y,z | ARRAY[0..3] OF BYTE | 0,0,0,0 |
Master IP for Write restriction 4) | No master IP Master IP |
0,0,0,0 W,X,y,z | ARRAY[0..3] OF BYTE | 0,0,0,0 |
Timeout for Bus supervision | No supervision 10 ms timeout 20 ms timeout |
0 1 2 |
BYTE | No supervision |
IO Mapping Structure 3) | Fixed Mapping Dynamic Mapping |
0 1 |
BYTE | 0 |
Reserved | Internal | 0 | ARRAY[0..2] OF BYTE | 0,0,0 |
Check supply | off on |
0 1 |
BYTE | 1 |
Fast counter | 0 : 10:sup:3) |
0 : 10 |
BYTE | 0 |
1) With a faulty ID, the Modules reports a “parameter error” and does not perform cyclic process data transmission. 2) Counter operating modes, see description of the Fast Counter: Fast Counters 3) Fixed Mapping means each module has its own MODBUS registers for data transfer independent of the IO bus constellation. See : MODBUS TCP Registers Dynamic mapping means the structure of the IO Date is dependent on the I/O bus constellation. Each I/O bus expansion module starts directly after the module before on the next Word adress. 4) If none of the parameters is set all masters / clients in the network have read and write rights on the CI52x-MODTCP device and its connected expansion modules. If at least one parameter is set only the configured masters / clients have write rights on the CI52x-MODTCP device, all other masters / clients still have read access to the CI52x-MODTCP device. |
Setting | Description |
---|---|
On | Error LED (S-ERR) lights up at errors of all error classes, Failsafe-mode off |
Off by E4 | Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, Failsafe-mode off |
Off by E3 | Error LED (S-ERR) lights up at errors of error classes E1 and E2, Failsafe-mode off |
On +Failsafe | Error LED (S-ERR) lights up at errors of all error classes, Failsafe-mode on *) |
Off by E4 + Failsafe | Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, Failsafe-mode on *) |
Off by E3 + Failsafe | Error LED (S-ERR) lights up at errors of error classes E1 and E2, Failsafe-mode on *) |
*) The parameters Behaviour AO at comm. error and Behaviour DO at comm. error are only analyzed if the Failsafe-mode is ON. |