Status LEDs¶
The LEDs are located at the front of module. There are 2 different groups:
- The 5 system LEDs (PWR, STA1 ETH, STA2 ETH, S-ERR and I/O-Bus) show the operation status of the module and display possible errors.
- The 27 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process supply voltage and the states of the inputs and outputs and display possible errors.
LED | Color | OFF | ON | Flashing |
---|---|---|---|---|
PWR/RUN | Green | Process supply voltage missing | Internal supply voltage OK, module ready for communication with IO Controller | Start-up / preparing communication |
Yellow | — | — | — | |
STA1 ETH (System LED “BF”) |
Green | — | Device configured, cyclic data exchange running | Device configured, acyclic data exchange running |
Red | — | Communication error (timeout) appeared | IP address error | |
STA2 ETH (System LED “SF”) | Green | Device has valid parameters | Device is running parameterization sequenze | Device has no parameters |
Red | — | — | Device has invalid parameters | |
S-ERR | Red | No error | Internal error | – |
I/O-Bus | Green | No expansion modules connected or communication error | Expansion modules connected and operational | — |
ETH1 | Green | No connection at ETHERNET interface | Connected to ETHERNET interface | — |
Yellow | — | Device is transmitting telegrams | Device is transmitting telegrams | |
ETH2 | Green | No connection at ETHERNET interface | Connected to ETHERNET interface | — |
Yellow | — | Device is transmitting telegrams | Device is transmitting telegrams |
LED | Color | OFF | ON | Flashing |
---|---|---|---|---|
AI0 to AI3 | Yellow | Input is OFF | Input is ON (brightness depends on the value of the analog signal) | – |
AO0 to AO1 | Yellow | Output is OFF | Output is ON (brightness depends on the value of the analog signal) | – |
DI0 to DI7 | Yellow | Input is OFF | Input is ON (the input voltage is even displayed if the supply voltage is OFF) | – |
DO0 toDO7 | Yellow | Output is OFF | Output is ON | – |
UP | Green | Process supply voltage missing | Process supply voltage OK and initialization finished | – |
UP3 | Green | Process supply voltage missing | Process supply voltage OK | – |
CH-ERR1 to CH-ERR3 | Red | No error or process supply voltage missing | Internal error | Error on one channel of the corresponding group |