Serial Interface COM1ΒΆ

The serial interface COM1 can be used for:

  • Online access (RS-232 programming interface for Automation_Builder software)
  • Free protocol
  • MODBUS RTU, client and server
  • CS31 system bus (RS-485), as master only

Serial Interface COM1 of the Terminal Bases.

Pin assignment

Serial Interface Pin Signal Interface Description
../_images/087d1a046426a5750a33139001f61359 1 FE - Functional earth
2 TxD RS-232 Transmit data Output
3 RxD/TxD-P RS-485 Receive/Transmit Positive
4 RTS RS-232 Request to send Output
5 SGND Signal ground 0 V supply out
6 +5 V - 5 V supply out
7 RxD RS-232 Receive data Input
8 RxD/TxD-N RS-485 Receive/Transmit Negative
9 CTS RS-232 Clear to send Input
Shield FE - Functional earth

Attention

:strong:Risk of corrosion!

Unused connectors and slots may corrode if XC devices are used in salt-mist environments.

Protect unused connectors and slots with TA535 protective caps for XC devices TA535: Protective Caps TA535 for XC Devices TA535 - Protective Caps for XC Devices.