Parameter | Value |
---|---|
Protocol | PROFINET I/O RT |
Bus connection | 2 x RJ45 (PNIO1 and PNIO2), with integrated 2-port switch |
Switch | Integrated |
Technology | Hilscher netX100 |
Transfer rate | 100 MBit/s (full-duplex) |
Transfer method | According to ETHERNET II, IEE802.3 |
Bus length (segment length max.) | 100 m |
Indicators | 5 LEDs |
Usable terminal bases | All TB5xx TB51x-TB54x |
Supported alarm types | Process alarm, diagnostic alarm, return of SubModule, plug alarm, pull alarm |
Current consumption from 24 V DC power supply at the terminal base of the CPU | Typ. 85 mA |
Internal supply | Via the communication module interface of the terminal base |
Setting of the I/O device identifier | With 2 rotary switches at the front side of the module |
Weight | Ca. 170 g |
Supported protocols | RTC - real-time cyclic protocol, class 1 RTA - real-time acyclic protocol DCP - discovery and configuration protocol * CL-RPC - connectionless remote procedure call LLDP - link layer discovery protocol SNMP - simply network management protocol MRP - MRP Client |
Acyclic services | PNIO read / write CM589-PNIO < FW 1.4.0: max. 1024 bytes CM589-PNIO ≥ FW 1.4.0: max. 8096 bytes CM589-PNIO-4: max. 8096 bytes |
Total quantity of input and output data | CM589-PNIO < FW 1.4.0 (respectively for input and output): max. 1024 byte CM589-PNIO ≥ FW 1.4.0 (respectively for input and output): max. 1440 byte CM589-PNIO-4 (respectively for input and output): max. 1440 byte |
Min. bus cycle | 1 ms |
Conformance class | CC B |
* Setting NameOfStation via service “DCP SET NameOfStation” is enabled only if rotary switches are adjusted to position “00”.