Technical DataΒΆ
The System Data of AC500-eCo apply System Data AC500-eCo
Only additional details are therefore documented below.
Parameter | Value | |
---|---|---|
Process supply voltage UP | ||
Connections | Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V) | |
Rated value | 24 V DC | |
Current consumption via UP terminal | 5 mA + max. 0.5 A per output | |
Max. ripple | 5 % | |
Inrush current | 0.000002 A:sup:2s | |
Protection against reversed voltage | Yes | |
Rated protection fuse for UP | Recommended; the outputs must be protected by an 3 A fast fuse | |
Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/bus module | Ca. 10 mA | |
Galvanic isolation | Yes, between the output group and the rest of the module | |
Isolated groups | 1 (8 channels per group) | |
Surge-voltage (max.) | 35 V DC for 0.5 s | |
Max. power dissipation within the module | On request | |
Weight | Ca. 115 g | |
Mounting position | Horizontal or vertical | |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
No effects of multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an external fuse.