Technical Data of the Analog \ Outputs

Parameter Value
Number of channels per module 2
Distribution of channels into groups 1 group for 2 channels
Connection of the channels AO0+…AO1+ Terminals 3.5 and 3.6
Reference potential for AO0+ to AO1+

Terminal 3.7 (AO-) for voltage output

Terminals 1.9, 2.9, 3.9 and 4.9 for current output

Output type  
  Unipolar Current
  Bipolar Voltage
Galvanic isolation Against internal supply and other modules
Configurability -10…+10 V, 0…20 mA, 4…20 mA (each output can be configured individually)

Output resistance (load),

as current output

0…500 W

Output loadability,

as voltage output

±10 mA max.
Indication of the output signals 1 LED per channel (brightness depends on the value of the analog signal)
Resolution 12 bits (+ sign)
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ. 0.5 %, max. 1 %
Relationship between input signal and hex code See Output Ranges Voltage and Current DA501 - Digital/Analog Input/Output Module
Unused outputs Are configured as “unused” (default value) and can be left open-circuited