Technical data of the digital inputs/outputs if used as outputs¶
| Parameter | Value | |
|---|---|---|
| Number of channels per module | 8 | |
| Distribution of the channels into groups | 1 group of 8 channels | |
| Terminals of the channels DC16 to DC23 | Terminals 4.0 to 4.7 | |
| Reference potential for all outputs | Terminals 1.9…4.9 (negative pole of the supply voltage, signal name ZP) | |
| Common power supply voltage | For all outputs terminals 1.8, 2.8, 3.8 and 4.8 (positive pole of the supply voltage, signal name UP) | |
| Output voltage for signal 1 | UP (-0.8 V) | |
| Output delay (0->1 or 1->0) | On request | |
| Output current | ||
| rated value per channel | 500 mA at UP = 24 V | |
| max. value (all channels together) | 4 A | |
| Leakage current with signal 0 | < 0.5 mA | |
| Fuse for UP | 10 A fast | |
| Demagnetization with inductive DC load | Via internal varistors (see figure below this table) | |
| Output switching frequency | ||
| With resistive load | On request | |
| With inductive loads | Max. 0.5 Hz | |
| With lamp loads | 11 Hz max. at 5 W max. | |
| Short-circuit-proof / overload-proof | Yes | |
| Overload message (I > 0.7 A) | Yes, after ca. 100 ms | |
| Output current limitation | Yes, automatic reactivation after short circuit/overload | |
| Resistance to feedback against 24V signals | Yes (software-controlled supervision) | |
| Max. cable length | ||
| Shielded | 1000 m | |
| Unshielded | 600 m | |
The following drawing shows the circuitry of a digital input/output with the varistors for demagnetization when inductive loads are switched off.
Digital input/output (circuit diagram)