Technical Data of the Analog Inputs¶
Parameter | Value | |
---|---|---|
Number of channels per module | 4 | |
Distribution of channels into groups | 1 group with 4 channels | |
Connection if channels AI0+ to AI3+ | Terminals 3.0 to 3.3 | |
Reference potential for AI0+ to AI3+ | Terminal 3.4 (AI-) for voltage and RTD measurement Terminal 1.9, 2.9, 3.9 and 4.9 for current measurement |
|
Input type | ||
Unipolar | Voltage 0 … 10 V, current or Pt100/Pt1000/Ni1000 | |
Bipolar | Voltage -10 … +10 V | |
Configurability | 0…10 V, -10…+10 V, 0/4…20 mA, Pt100/1000, Ni1000 (each input can be configured individually) | |
Channel input resistance | Voltage: > 100 kW, current: ca. 330 W | |
Time constant of the input filter | Voltage: 100 µs, current: 100 µs | |
Indication of the input signals | 1 LED per channel (brightness depends on the value of the analog signal) | |
Conversion cycle | 1 ms (for 4 inputs + 2 outputs); with RTDs Pt/Ni… 1 s | |
Resolution | Range 0…10 V: 12 Bits Range -10…+10 V: 12 Bits + sign Range 0…20 mA: 12 Bits Range 4…20 mA: 12 Bits Range RTD (Pt100, PT1000, Ni1000): 0.1 °C |
|
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range | Typ. 0.5 %, max. 1 % For XC version below 0 °C and above 60 °C: on request |
|
Relationship between input signal and hex code | Tables Input Ranges Voltage, Current and Digital Input DA501 - Digital/Analog Input/Output Module and Input Range Resistor DA501 - Digital/Analog Input/Output Module | |
Unused inputs | Are configured as “unused” (default value) | |
Overvoltage protection | Yes |