Technical Data of the Module¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
Parameter | Value | |
---|---|---|
Process supply voltage | ||
Connections | Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24 V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0 V) | |
Protection against reverse voltage | yes | |
Rated protection fuse at UP | 10 A fast | |
Rated value | 24 V DC | |
Max. ripple | 5 % | |
Current consumption | ||
From UP | 0.07 A + max. 0.5 A per output | |
From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module | ca. 2 mA | |
Inrush current from UP (at power-up) | 0.04 A:sup:2s | |
Galvanic isolation | Yes, per module | |
Max. power dissipation within the module | 6 W (outputs unloaded) | |
Input data length | 12 bytes | |
Output data length | 8 bytes | |
Weight (without terminal unit) | ca. 125 g | |
Mounting position | Horizontal mounting or vertical with derating (output load reduced to 50 % at 40 °C) | |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Attention
:strong:Attention:
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.
No effects of multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an internal smart high-side switch.