Technical Data of the Module

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Parameter Value
Process supply voltage  
  Connections Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24 V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0 V)
  Protection against reverse voltage yes
  Rated protection fuse at UP 10 A fast
  Rated value 24 V DC
  Max. ripple 5 %
Current consumption  
  From UP 0.07 A + max. 0.5 A per output
  From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module ca. 2 mA
  Inrush current from UP (at power-up) 0.04 A:sup:2s
Galvanic isolation Yes, per module
Max. power dissipation within the module 6 W (outputs unloaded)
Input data length 12 bytes
Output data length 8 bytes
Weight (without terminal unit) ca. 125 g
Mounting position Horizontal mounting or vertical with derating (output load reduced to 50 % at 40 °C)
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.

No effects of multiple overloads

No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an internal smart high-side switch.