Serial Interfaces COM1/COM2ΒΆ

Serial Interface COM1

The serial interface COM1 is connected to a removable 9-pin terminal block. It is configurable for RS-232 and RS-485 and can be used (depending on the processor module) for:

  • Online access (RS-232 programming interface for Automation_Builder)
  • A free protocol
  • MODBUS RTU, client and server
  • CS31 system bus (RS-485), as master only CS31 system bus

Pin assignment

  Pin Signal Interface Description
../_images/fb4eeb4f76235e580a317f346fcb7657

Terminal block removed

../_images/fdf498867622e2270a317f347dd03ca3

Terminal block inserted

1 Terminator P RS-485 Terminator P
2 RxD/TxD-P RS-485 Receive/Transmit, positive
3 RxD/TxD-N RS-485 Receive/Transmit, negative
4 Terminator N RS-485 Terminator N
5 RTS RS-232 Request to send (output)
6 TxD RS-232 Transmit data (output)
7 SGND Signal Ground Signal Ground
8 RxD RS-232 Receive data (input)
9 CTS RS-232 Clear to send (input)

Attention

:strong:Unused connector!

Make sure that the terminal block is always connected to the terminal base, even if you do not use the interface.

Serial Interface COM2

The serial interface COM2 is connected to a 9-pin D-sub connector. It is configurable for RS-232 and RS-485 and can be used (depending on the processor module) for:

  • Online access (RS-232 programming interface for Automation_Builder)
  • A free protocol
  • MODBUS RTU, client and server

COM2 is not intended to establish a CS31 system bus.

Note

TB5x3-2ETH terminal bases have no COM2 D-sub connector.

Pin assignment

Serial Interface Pin Signal Interface Description
../_images/087d1a046426a5750a33139001f61359 1 FE - Functional earth
2 TxD RS-232 Transmit data Output
3 RxD/TxD-P RS-485 Receive/Transmit Positive
4 RTS RS-232 Request to send Output
5 SGND Signal ground 0 V supply out
6 +5 V - 5 V supply out
7 RxD RS-232 Receive data Input
8 RxD/TxD-N RS-485 Receive/Transmit Negative
9 CTS RS-232 Clear to send Input
Shield FE - Functional earth

Attention

:strong:Risk of corrosion!

Unused connectors and slots may corrode if XC devices are used in salt-mist environments.

Protect unused connectors and slots with TA535 protective caps for XC devices TA535: Protective Caps TA535 for XC Devices TA535 - Protective Caps for XC Devices.