Technical Data¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
Processor Module and Terminal Base
| Parameter | Value |
|---|---|
| Connection of the supply voltage 24 VDC at the terminal base of the processor module | Removable 5-pin terminal block with spring connection |
| Current consumption from 24 VDC | PM57x: 50 mA PM57x-ETH: 110 mA |
PM58x: 50 mA PM58x-ETH: 110 mA PM58x-ARCNET: 110 mA |
|
PM59x: 90 mA PM59x-ETH: 150 mA PM59x-2ETH: 150 mA PM59x-ARCNET: 150 mA |
|
| Fuse melting integral at 24 VDC | Min. 1 A²s 1) |
| Max. input power from 24 VDC | 10 W 2) |
| Slots on the terminal bases | TB511: 1 processor module, 1 communication module |
| TB521 / TB523: 1 processor module, 2 communication modules | |
| TB541: 1 processor module, 4 communication modules | |
| Processor module interfaces at the terminal bases TB5x1 | I/O bus, COM1, COM2, FBP |
| Processor module interfaces at the terminal bases TB5x3 | I/O bus, COM1 |
| Processor module network interfaces at the terminal bases | TB5x1-ETH TB51x-TB54x / PM5xx-ETH: ETHERNET |
| TB5x3-ETH TB51x-TB54x/ PM5xx-ETH: 2x ETHERNET | |
| TB5x1-ARCNET TB51x-TB54x/ PM5xx-ARCNET: ARCNET | |
| Connection system | see System Assembly, Construction and Connection AC500 (Standard) |
| Weight (processor module without terminal base) | PM582: 135 g PM58x-ETH: 150 g |
PM59x: 135 g PM59x-ETH: 150 g PM59x-2ETH: 150 g PM59x-ARCNET: 160 g |
|
| Mounting position | Horizontal or vertical |
| 1) | The inrush current and the melting integral of the processor module depends on the processor module’s integrated power supply, and the number and type of communication modules and I/O modules connected to the I/O bus. The values are valid for all processor modules. |
| 2) | Including communication modules and I/O bus modules |
Detailed Data
| Processor Module | PM572 | PM573-ETH | |
|---|---|---|---|
| Program memory flash EPROM and RAM | 128 kB | 512 kB | |
| Data memory, integrated | 128 kB, incl. 12 kB buffered | 512 kB, incl. 288 kB buffered | |
| Expandable memory | None | None | |
| Integrated mass storage memory | None | None | |
| Pluggable memory card for: | |||
| User data storage | x | x | |
| Program storage | x | x | |
| Firmware update | x | x | |
| Cycle time for 1 instruction: | |||
| Binary | Min. 0.06 µs | Min. 0.06 µs | |
| Word | Min. 0.09 µs | Min. 0.09 µs | |
| Floating point | Min. 0.70 µs | Min. 0.70 µs | |
| Max. number of central inputs and outputs (up to 7 exp. modules): (1) | |||
| Digital inputs | 224 | 224 | |
| Digital outputs | 224 | 224 | |
| Analog inputs | 112 | 112 | |
| Analog outputs | 112 | 112 | |
| Max. number of central inputs and outputs (10 exp. modules): | |||
| Digital inputs | 320 | 320 | |
| Digital outputs | 320 | 320 | |
| Analog inputs | 160 | 160 | |
| Analog outputs | 160 | 160 | |
| Number of decentralized inputs and outputs | Depends on the fieldbus used (as an info on the CS31 bus: up to 31 stations with up to 120 DI / 120 DO each) |
||
| Data backup | Battery | ||
| Data buffering time at 25 °C | Typ. 3 years without power supply | ||
| Battery low indication | Warning issued about 2 weeks before the state of charge becomes critical | ||
| Real-time clock: | |||
| With battery back-up | x | x | |
| Accuracy | Typ. ± 2 s / day at 25 °C | ||
| Program execution: | |||
| Cyclic | x | x | |
| Time-controlled | x | x | |
| Multitasking | x | x | |
| Protection of the user program by a password | x | x | |
| Serial interface COM1: | |||
| Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) pluggable terminal block, spring connection for programming, as MODBUS (master/slave), as serial ASCI communication, as CS31 Master | ||
| Connection | |||
| Usage | |||
| Serial interface COM2 (not for PM5xy-2ETH models): | |||
| Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) D-sub for programming, as MODBUS (master/slave), as serial ASCII communication | ||
| Connection | |||
| Usage | |||
| Integrated communication module: | |||
| ETH = ETHERNET | - | ETH onboard with web server, SNTP and IEC60870-5-104 protocol | |
| RJ45 | - | ||
| ARCNET = ARCNET BNC | - | ||
| Number of external communication modules | Up to 4 communication modules like PROFIBUS DP, ETHERNET, CANOPEN. There are no restrictions concerning the communication module types and communication module combinations (e.g. up to 4 PROFIBUS DP communication modules are possible) | ||
| LEDs, LCD display, 8 function keys | For RUN/STOP switchover, status displays and diagnosis | ||
| Number of timers | Unlimited | ||
| Number of counters | Unlimited | ||
| Programming languages: | |||
| Structured Text ST | x | x | |
| Instruction List IL | x | x | |
| Function Block Diagram FBD | x | x | |
| Ladder Diagram LD | x | x | |
| Sequential Function Chart SFC | x | x | |
| Continuous Function Chart CFC | x | x | |
| 1): up to 7 I/O terminal units before PS501 V1.2 and processor module firmware before V1.2.0. | |||
| Processor Module | PM582 | PM583-ETH | PM585-ETH | |
|---|---|---|---|---|
| Program memory flash EPROM and RAM | 512 kB | 1024 kB | 1024 kB | |
| Data memory, integrated | 416 kB, incl. 288 kB buffered | 1024 kB, incl. 288 kB buffered | 1536 kB, incl. 512 kB buffered | |
| Expandable memory | None | None | None | |
| Integrated mass storage memory | None | None | None | |
| Pluggable memory card for: | ||||
| User data storage | x | x | x | |
| Program storage | x | x | x | |
| Firmware update | x | x | x | |
| Cycle time for 1 instruction: | ||||
| Binary | Min. 0.05 µs | Min. 0.004 µs | ||
| Word | Min. 0.06 µs | Min. 0.008 µs | ||
| Floating point | Min. 0.50 µs | Min. 0.008 µs | ||
| Max. number of central inputs and outputs (up to 7 exp. modules): 1) | ||||
| Digital inputs | 224 | |||
| Digital outputs | 224 | |||
| Analog inputs | 112 | |||
| Analog outputs | 112 | |||
| Max. number of central inputs and outputs (10 exp. modules): | ||||
| Digital inputs | 320 | |||
| Digital outputs | 320 | |||
| Analog inputs | 160 | |||
| Analog outputs | 160 | |||
| Number of decentralized inputs and outputs | Depends on the fieldbus used (as an info on the CS31 bus: up to 31 stations with up to 120 DI / 120 DO each) |
|||
| Data backup | Battery | |||
| Data buffering time at 25 °C | Typ. 3 years without power supply | |||
| Battery low indication | Warning issued about 2 weeks before the state of charge becomes critical | |||
| Real-time clock: | ||||
| With battery back-up | x | |||
| Accuracy | Typ. ± 2 s / day at 25 °C | |||
| Program execution: | ||||
| Cyclic | x | |||
| Time-controlled | x | |||
| Multitasking | x | |||
| Protection of the user program by a password | x | |||
| Serial interface COM1: | ||||
| Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) pluggable terminal block, spring connection for programming, as MODBUS (master/slave), as serial ASCI communication, as CS31 master | |||
| Connection | ||||
| Usage | ||||
| Serial interface COM2 (not for PM5xy-2ETH models): | ||||
| Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) D-sub for programming, as MODBUS (master/slave), as serial ASCII communication | |||
| Connection | ||||
| Usage | ||||
| Integrated communication module: | ||||
| ETH = ETHERNET | - | ETH onboard with web server, SNTP and IEC60870-5-104 protocol | ||
| RJ45 | - | |||
| ARCNET = ARCNET BNC | - | |||
| Number of external communication modules | Up to 4 communication modules like PROFIBUS DP, ETHERNET, CANOPEN. There are no restrictions concerning the communication module types and communication module combinations (e.g. up to 4 PROFIBUS DP communication modules are possible) | |||
| LEDs, LCD display, 8 Function Keys | For RUN/STOP switchover, status displays and diagnosis | |||
| Number of timers | Unlimited | |||
| Number of counters | Unlimited | |||
| Programming languages: | ||||
| Structured Text ST | x | |||
| Instruction List IL | x | |||
| Function Block Diagram FBD | x | |||
| Ladder Diagram LD | x | |||
| Sequential Function Chart SFC | x | |||
| Continuous Function Chart (CFC) | x | |||
| 1): up to 7 I/O terminal units before PS501 V1.2 and processor module firmware before V1.2.0. | ||||
| Processor Module | PM59x-ETH | PM59x-ARCNET | PM59x-ETH PM59x-2ETH |
|
|---|---|---|---|---|
| Program memory flash EPROM and RAM | PM590: 2048 kB PM591/PM592: 4096 kB |
|||
| Data memory, integrated | PM590: 2560 kB, PM591: 3584 kB, incl. 1536 kB buffered |
PM590: 3072 kB, PM591/592: 5632 kB, incl. 1536 kB buffered |
||
| Expandable memory | None | None | None | |
| Integrated mass storage memory | None | None | PM592-ETH: 4 GB flash disk | |
| Pluggable memory card for: | ||||
| User data storage | x | x | x | |
| Program storage | x | x | x | |
| Firmware update | x | x | x | |
| Cycle time for 1 instruction: | ||||
| Binary | Min. 0.002 µs | Min. 0.002 µs | Min. 0.002 µs | |
| Word | Min. 0.004 µs | Min. 0.004 µs | Min. 0.004 µs | |
| Floating point | Min. 0.004 µs | Min. 0.004 µs | Min. 0.004 µs | |
| Max. number of central inputs and outputs (up to 7 exp. modules): 1) | ||||
| Digital inputs | 224 | 224 | 224 | |
| Digital outputs | 224 | 224 | 224 | |
| Analog inputs | 112 | 112 | 112 | |
| Analog outputs | 112 | 112 | 112 | |
| Max. number of central inputs and outputs (10 exp. modules): | ||||
| Digital inputs | 320 | 320 | 320 | |
| Digital outputs | 320 | 320 | 320 | |
| Analog inputs | 160 | 160 | 160 | |
| Analog outputs | 160 | 160 | 160 | |
| Number of decentralized inputs and outputs | Depends on the fieldbus used (as an info on the CS31 bus: up to 31 stations with up to 120 DI / 120 DO each) |
|||
| Data backup | Battery | |||
| Data buffering time at 25 °C | Typ. 3 years without power supply | |||
| Battery low indication | Warning issued about 2 weeks before the state of charge becomes critical | |||
| Real-time clock: | ||||
| With battery back-up | x | x | x | |
| Accuracy | Typ. ± 2 s / day at 25 °C | Typ. ± 2 s / day at 25 °C | Typ. ± 2 s / day at 25 °C | |
| Program execution: | ||||
| Cyclic | x | x | x | |
| Time-controlled | x | x | x | |
| Multitasking | x | x | x | |
| Password protection of user program | x | x | x | |
| Serial interface COM1: | ||||
| Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) pluggable terminal block, spring connection for programming, as MODBUS (master/slave), as serial ASCII communication, as CS31 master | |||
| Connection | ||||
| Usage | ||||
| Serial interface COM2 (not for PM5xy-2ETH models): | ||||
| Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) D-sub for programming, as MODBUS (master/slave), as serial ASCII communication | |||
| Connection | ||||
| Usage | ||||
| Integrated communication module: | ||||
| ETH = ETHERNET | ETH | ARCNET | ETH onboard with Webserver, SNTP and IEC60870-5-104 protocol | |
| RJ45 | ETH | ARCNET | ||
| ARCNET = ARCNET BNC | ETH | ARCNET | ||
| Number of external communication modules | Up to 4 communication modules like PROFIBUS DP, ETHERNET, CANOPEN. There are no restrictions concerning the communication module types and communication module combinations (e.g. up to 4 PROFIBUS DP communication modules are possible) | |||
| LEDs, LCD display, 8 Function Keys | For RUN/STOP switchover, status displays and diagnosis | |||
| Number of timers | Unlimited | Unlimited | Unlimited | |
| Number of counters | Unlimited | Unlimited | Unlimited | |
| Programming languages: | ||||
| Structured Text ST | x | x | x | |
| Instruction List IL | x | x | x | |
| Function Block Diagram FBD | x | x | x | |
| Ladder Diagram LD | x | x | x | |
| Sequential Function Chart SFC | x | x | x | |
| Continuous Function Chart (CFC) | x | x | x | |
| 1) | Up to 7 I/O terminal units before PS501 V1.2 and processor module firmware before V1.2.0. |
| 2) | For PM595 see device description for PM595 PM595. |