Technical Data¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
Processor Module and Terminal Base
Parameter | Value |
---|---|
Connection of the supply voltage 24 VDC at the terminal base of the processor module | Removable 5-pin terminal block with spring connection |
Current consumption from 24 VDC | PM57x: 50 mA PM57x-ETH: 110 mA |
PM58x: 50 mA PM58x-ETH: 110 mA PM58x-ARCNET: 110 mA |
|
PM59x: 90 mA PM59x-ETH: 150 mA PM59x-2ETH: 150 mA PM59x-ARCNET: 150 mA |
|
Fuse melting integral at 24 VDC | Min. 1 A²s 1) |
Max. input power from 24 VDC | 10 W 2) |
Slots on the terminal bases | TB511: 1 processor module, 1 communication module |
TB521 / TB523: 1 processor module, 2 communication modules | |
TB541: 1 processor module, 4 communication modules | |
Processor module interfaces at the terminal bases TB5x1 | I/O bus, COM1, COM2, FBP |
Processor module interfaces at the terminal bases TB5x3 | I/O bus, COM1 |
Processor module network interfaces at the terminal bases | TB5x1-ETH TB51x-TB54x / PM5xx-ETH: ETHERNET |
TB5x3-ETH TB51x-TB54x/ PM5xx-ETH: 2x ETHERNET | |
TB5x1-ARCNET TB51x-TB54x/ PM5xx-ARCNET: ARCNET | |
Connection system | see System Assembly, Construction and Connection AC500 (Standard) |
Weight (processor module without terminal base) | PM582: 135 g PM58x-ETH: 150 g |
PM59x: 135 g PM59x-ETH: 150 g PM59x-2ETH: 150 g PM59x-ARCNET: 160 g |
|
Mounting position | Horizontal or vertical |
1) | The inrush current and the melting integral of the processor module depends on the processor module’s integrated power supply, and the number and type of communication modules and I/O modules connected to the I/O bus. The values are valid for all processor modules. |
2) | Including communication modules and I/O bus modules |
Detailed Data
Processor Module | PM572 | PM573-ETH | |
---|---|---|---|
Program memory flash EPROM and RAM | 128 kB | 512 kB | |
Data memory, integrated | 128 kB, incl. 12 kB buffered | 512 kB, incl. 288 kB buffered | |
Expandable memory | None | None | |
Integrated mass storage memory | None | None | |
Pluggable memory card for: | |||
User data storage | x | x | |
Program storage | x | x | |
Firmware update | x | x | |
Cycle time for 1 instruction: | |||
Binary | Min. 0.06 µs | Min. 0.06 µs | |
Word | Min. 0.09 µs | Min. 0.09 µs | |
Floating point | Min. 0.70 µs | Min. 0.70 µs | |
Max. number of central inputs and outputs (up to 7 exp. modules): (1) | |||
Digital inputs | 224 | 224 | |
Digital outputs | 224 | 224 | |
Analog inputs | 112 | 112 | |
Analog outputs | 112 | 112 | |
Max. number of central inputs and outputs (10 exp. modules): | |||
Digital inputs | 320 | 320 | |
Digital outputs | 320 | 320 | |
Analog inputs | 160 | 160 | |
Analog outputs | 160 | 160 | |
Number of decentralized inputs and outputs | Depends on the fieldbus used (as an info on the CS31 bus: up to 31 stations with up to 120 DI / 120 DO each) |
||
Data backup | Battery | ||
Data buffering time at 25 °C | Typ. 3 years without power supply | ||
Battery low indication | Warning issued about 2 weeks before the state of charge becomes critical | ||
Real-time clock: | |||
With battery back-up | x | x | |
Accuracy | Typ. ± 2 s / day at 25 °C | ||
Program execution: | |||
Cyclic | x | x | |
Time-controlled | x | x | |
Multitasking | x | x | |
Protection of the user program by a password | x | x | |
Serial interface COM1: | |||
Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) pluggable terminal block, spring connection for programming, as MODBUS (master/slave), as serial ASCI communication, as CS31 Master | ||
Connection | |||
Usage | |||
Serial interface COM2 (not for PM5xy-2ETH models): | |||
Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) D-sub for programming, as MODBUS (master/slave), as serial ASCII communication | ||
Connection | |||
Usage | |||
Integrated communication module: | |||
ETH = ETHERNET | - | ETH onboard with web server, SNTP and IEC60870-5-104 protocol | |
RJ45 | - | ||
ARCNET = ARCNET BNC | - | ||
Number of external communication modules | Up to 4 communication modules like PROFIBUS DP, ETHERNET, CANOPEN. There are no restrictions concerning the communication module types and communication module combinations (e.g. up to 4 PROFIBUS DP communication modules are possible) | ||
LEDs, LCD display, 8 function keys | For RUN/STOP switchover, status displays and diagnosis | ||
Number of timers | Unlimited | ||
Number of counters | Unlimited | ||
Programming languages: | |||
Structured Text ST | x | x | |
Instruction List IL | x | x | |
Function Block Diagram FBD | x | x | |
Ladder Diagram LD | x | x | |
Sequential Function Chart SFC | x | x | |
Continuous Function Chart CFC | x | x | |
1): up to 7 I/O terminal units before PS501 V1.2 and processor module firmware before V1.2.0. |
Processor Module | PM582 | PM583-ETH | PM585-ETH | |
---|---|---|---|---|
Program memory flash EPROM and RAM | 512 kB | 1024 kB | 1024 kB | |
Data memory, integrated | 416 kB, incl. 288 kB buffered | 1024 kB, incl. 288 kB buffered | 1536 kB, incl. 512 kB buffered | |
Expandable memory | None | None | None | |
Integrated mass storage memory | None | None | None | |
Pluggable memory card for: | ||||
User data storage | x | x | x | |
Program storage | x | x | x | |
Firmware update | x | x | x | |
Cycle time for 1 instruction: | ||||
Binary | Min. 0.05 µs | Min. 0.004 µs | ||
Word | Min. 0.06 µs | Min. 0.008 µs | ||
Floating point | Min. 0.50 µs | Min. 0.008 µs | ||
Max. number of central inputs and outputs (up to 7 exp. modules): 1) | ||||
Digital inputs | 224 | |||
Digital outputs | 224 | |||
Analog inputs | 112 | |||
Analog outputs | 112 | |||
Max. number of central inputs and outputs (10 exp. modules): | ||||
Digital inputs | 320 | |||
Digital outputs | 320 | |||
Analog inputs | 160 | |||
Analog outputs | 160 | |||
Number of decentralized inputs and outputs | Depends on the fieldbus used (as an info on the CS31 bus: up to 31 stations with up to 120 DI / 120 DO each) |
|||
Data backup | Battery | |||
Data buffering time at 25 °C | Typ. 3 years without power supply | |||
Battery low indication | Warning issued about 2 weeks before the state of charge becomes critical | |||
Real-time clock: | ||||
With battery back-up | x | |||
Accuracy | Typ. ± 2 s / day at 25 °C | |||
Program execution: | ||||
Cyclic | x | |||
Time-controlled | x | |||
Multitasking | x | |||
Protection of the user program by a password | x | |||
Serial interface COM1: | ||||
Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) pluggable terminal block, spring connection for programming, as MODBUS (master/slave), as serial ASCI communication, as CS31 master | |||
Connection | ||||
Usage | ||||
Serial interface COM2 (not for PM5xy-2ETH models): | ||||
Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) D-sub for programming, as MODBUS (master/slave), as serial ASCII communication | |||
Connection | ||||
Usage | ||||
Integrated communication module: | ||||
ETH = ETHERNET | - | ETH onboard with web server, SNTP and IEC60870-5-104 protocol | ||
RJ45 | - | |||
ARCNET = ARCNET BNC | - | |||
Number of external communication modules | Up to 4 communication modules like PROFIBUS DP, ETHERNET, CANOPEN. There are no restrictions concerning the communication module types and communication module combinations (e.g. up to 4 PROFIBUS DP communication modules are possible) | |||
LEDs, LCD display, 8 Function Keys | For RUN/STOP switchover, status displays and diagnosis | |||
Number of timers | Unlimited | |||
Number of counters | Unlimited | |||
Programming languages: | ||||
Structured Text ST | x | |||
Instruction List IL | x | |||
Function Block Diagram FBD | x | |||
Ladder Diagram LD | x | |||
Sequential Function Chart SFC | x | |||
Continuous Function Chart (CFC) | x | |||
1): up to 7 I/O terminal units before PS501 V1.2 and processor module firmware before V1.2.0. |
Processor Module | PM59x-ETH | PM59x-ARCNET | PM59x-ETH PM59x-2ETH |
|
---|---|---|---|---|
Program memory flash EPROM and RAM | PM590: 2048 kB PM591/PM592: 4096 kB |
|||
Data memory, integrated | PM590: 2560 kB, PM591: 3584 kB, incl. 1536 kB buffered |
PM590: 3072 kB, PM591/592: 5632 kB, incl. 1536 kB buffered |
||
Expandable memory | None | None | None | |
Integrated mass storage memory | None | None | PM592-ETH: 4 GB flash disk | |
Pluggable memory card for: | ||||
User data storage | x | x | x | |
Program storage | x | x | x | |
Firmware update | x | x | x | |
Cycle time for 1 instruction: | ||||
Binary | Min. 0.002 µs | Min. 0.002 µs | Min. 0.002 µs | |
Word | Min. 0.004 µs | Min. 0.004 µs | Min. 0.004 µs | |
Floating point | Min. 0.004 µs | Min. 0.004 µs | Min. 0.004 µs | |
Max. number of central inputs and outputs (up to 7 exp. modules): 1) | ||||
Digital inputs | 224 | 224 | 224 | |
Digital outputs | 224 | 224 | 224 | |
Analog inputs | 112 | 112 | 112 | |
Analog outputs | 112 | 112 | 112 | |
Max. number of central inputs and outputs (10 exp. modules): | ||||
Digital inputs | 320 | 320 | 320 | |
Digital outputs | 320 | 320 | 320 | |
Analog inputs | 160 | 160 | 160 | |
Analog outputs | 160 | 160 | 160 | |
Number of decentralized inputs and outputs | Depends on the fieldbus used (as an info on the CS31 bus: up to 31 stations with up to 120 DI / 120 DO each) |
|||
Data backup | Battery | |||
Data buffering time at 25 °C | Typ. 3 years without power supply | |||
Battery low indication | Warning issued about 2 weeks before the state of charge becomes critical | |||
Real-time clock: | ||||
With battery back-up | x | x | x | |
Accuracy | Typ. ± 2 s / day at 25 °C | Typ. ± 2 s / day at 25 °C | Typ. ± 2 s / day at 25 °C | |
Program execution: | ||||
Cyclic | x | x | x | |
Time-controlled | x | x | x | |
Multitasking | x | x | x | |
Password protection of user program | x | x | x | |
Serial interface COM1: | ||||
Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) pluggable terminal block, spring connection for programming, as MODBUS (master/slave), as serial ASCII communication, as CS31 master | |||
Connection | ||||
Usage | ||||
Serial interface COM2 (not for PM5xy-2ETH models): | ||||
Physical link | Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s) D-sub for programming, as MODBUS (master/slave), as serial ASCII communication | |||
Connection | ||||
Usage | ||||
Integrated communication module: | ||||
ETH = ETHERNET | ETH | ARCNET | ETH onboard with Webserver, SNTP and IEC60870-5-104 protocol | |
RJ45 | ETH | ARCNET | ||
ARCNET = ARCNET BNC | ETH | ARCNET | ||
Number of external communication modules | Up to 4 communication modules like PROFIBUS DP, ETHERNET, CANOPEN. There are no restrictions concerning the communication module types and communication module combinations (e.g. up to 4 PROFIBUS DP communication modules are possible) | |||
LEDs, LCD display, 8 Function Keys | For RUN/STOP switchover, status displays and diagnosis | |||
Number of timers | Unlimited | Unlimited | Unlimited | |
Number of counters | Unlimited | Unlimited | Unlimited | |
Programming languages: | ||||
Structured Text ST | x | x | x | |
Instruction List IL | x | x | x | |
Function Block Diagram FBD | x | x | x | |
Ladder Diagram LD | x | x | x | |
Sequential Function Chart SFC | x | x | x | |
Continuous Function Chart (CFC) | x | x | x |