Technical Data¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
| Parameter | Value | |
|---|---|---|
| Connection of the supply voltage 24 V DC at the TF5x1_CMS | The terminals 1.8, 4.8…7.8, 1.9, 4.9…7.9, 4.0…4.7, 7.0…7.7 are electrically interconnected within the TF5x1_CMS. Terminals 1.8, 4.8…7.8: process voltage L+ = +24 V DC Terminals 1.9, 4.9…7.9: process voltage M = 0 V Terminals 4.0…4.7, 7.0…7.7: analog shield clamps SH Terminal 1.0: FE shield clamp of encoder |
|
| Rated voltage | 24 V DC | |
| Max. permitted total current | 10 A (between terminals 1.8, 4.8…7.8 and 1.9, 4.9…7.9) | |
| Slots | ||
| TF501_CMS | 1 function module FM502_CMS, 1 processor module PM592_ETH, 0 communication modules | |
| TF521_CMS | 1 function module FM502_CMS, 1 processor module PM592_ETH, 2 communication modules | |
| Processor module interfaces | I/O bus, COM1 | |
| Weight | TF501_CMS: 350 g | |
| TF521_CMS: 400 g | ||
| Mounting position | Horizontal or vertical | |
| Parameter | Value |
|---|---|
| I/O bus | I/O interface for directly adding up to 10 terminal units |
| Terminal block | 70 clamps for I/O, shield and power supply connection |
| COM1 | Serial interface, 9-pin D-sub connector, female |
Network interface (type must be equal to the type of the used processor module) |
ETHERNET RJ45 |