Environmental Conditions¶
Parameter | Value | |
---|---|---|
24 V DC | ||
Voltage | 24 V (-15 %, +20 %) | |
Protection against reverse polarity | Yes | |
120 V AC | ||
Voltage | 120 V (-15 %, +10 %) | |
Frequency | 50/60 Hz (-6 %, +4 %) | |
230 V AC | ||
Voltage | 230 V AC (-15 %, +10 %) | |
Frequency | 50/60 Hz (-6 %, +4 %) | |
120…240 V AC wide range supply | ||
Voltage | 120…240 V (-15 %, +10 %) | |
Frequency | 50/60 Hz (-6 %, +4 %) | |
Allowed interruptions of power supply, according to EN 61131-2 | ||
DC supply | Interruption < 10 ms, time between 2 interruptions > 1 s, PS2 | |
AC supply | Interruption < 0.5 periods, time between 2 interruptions > 1 s |
Attention
Exceeding the maximum power supply voltage for process or supply voltages could lead to unrecoverable damage of the system. The system could be destroyed.
Attention
Improper voltage level or frequency range which cause damage of AC inputs:
- AC voltage above 264 V
- Frenquency below 47 Hz or above 62.4 Hz
Attention
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable temperature classification.
Parameter | Value | |
---|---|---|
Temperature | ||
Operating | 0 °C … +60 °C: Horizontal mounting of modules. 0 °C … +40 °C: Vertical mounting of modules. Output load reduced to 50 % per group. |
|
Storage | -40 °C … +70 °C | |
Transport | -40 °C … +70 °C | |
Humidity | Max. 95 %, without condensation | |
Air pressure | ||
Operating | > 800 hPa / < 2000 m | |
Storage | > 660 hPa / < 3500 m | |
Ingress protection | IP20 |