Structure of the Diagnosis Block via PNIO_DEV_ALARM \ Function Block

Byte Number Description Possible Values
1 Diagnosis Byte, slot number

31 = CI501-PNIO (e. g. error at integrated 8 DI / 8 DO)

1 = 1st connected S500 I/O Module

10 = 10th connected S500 I/O Module

2 Diagnosis Byte, module number According to the I/O Bus specification passed on by modules to the fieldbus master
3 Diagnosis Byte, channel According to the I/O Bus specification passed on by modules to the fieldbus master
4 Diagnosis Byte, error code

According to the I/O Bus specification

Bit 7 and bit 6, coded error class

0 = E1

1 = E2

2 = E3

3 = E4

Bit 0 to Bit 5, coded error description

5 Diagnosis Byte, flags

According to the I/O-Bus specification

Bit 7: 1 = coming error

Bit 6: 1 = leaving error

In cases of short circuit or overload, the digital outputs are turned off. The modules performs reactivation automatically. Thus an acknowledgement of the errors is not necessary. The error message is stored via the LED.

E1..E4 d1 d2 d3 d4

Identifier

000..063

AC500-Display <− Display in
Class Comp Dev Mod Ch Err PS501 PLC Browser

Byte 4

Bit 6..7

- Byte 1 Byte 2 Byte 3

Byte 4

Bit 0..5

PNIO diagnosis block
Class Interface Device Module Channel

Error-

Identifier

Error message Remedy
  1) 2) 3)        
Module errors
3 - 31 31 31 19 Checksum error in the I/O module Replace I/O module
3 - 31 31 31 3 Timeout in the I/O module
3 - 31 31 31 40 Different hard-/firmware versions in the module
3 - 31 31 31 43 Internal error in the module
3 - 31 31 31 36 Internal data exchange failure
3 - 31 31 31 9 Overflow diagnosis buffer Restart
3 - 31 31 31 26 Parameter error Check Master
3 - 31 31 31 11 Process voltage UP too low Check process supply voltage
3 - 31 31 31 45 No process voltage UP Check process supply voltage
3 - 31 31/1..10 31 17 No communication with I/O device Replace I/O module
3 - 31 1..10 31 32 Wrong I/O device type on socket Replace I/O module / Check configuration
4 - 31 1..10 31 31 At least one module does not support failsafe function Check modules and parameterization
4 - 31 31 31 46 Voltage feedback on activated digital outputs DO0..DO7 on UP3 4) Check terminals
4 - 31/1…10 31 31 34 No response during initialization of the I/O module Replace I/O module
4 - 31 31 31 11 Process voltage UP3 too low Check process supply voltage
4 1…6 255 2 0 45 The connected Communication Module has no connection to the network Check cabeling
4 - 31 31 31 45 No process voltage UP3 Check process supply voltage
4 - 31 31 31 10 Voltage overflow on outputs (above UP3 level) 5) Check terminals/ check process supply voltage
Channel error digital
4 - 31 2 0…7 46 Externally voltage detected at digital output DO0..DO7 6) Check terminals
4 - 31 2 0…7 47 Short circuit at digital output 7) Check terminals
Channel error analog
4 - 31 1 0..3 48 Analog value overflow or broken wire at an analog input Check value or check terminals
4 - 31 1 0..3 7 Analog value underflow at an analog input Check value
4 - 31 1 0..3 47 Short-circuit at an analog input Check terminals
4 - 31 3 0..1 4 Analog value overflow at an analog output Check output value
4 - 31 3 0..1 7 Analog value underflow at an analog output Check output value

Remarks:

1)

In AC500 the following interface identifier applies:

“-” = Diagnosis via bus-specific function blocks; 0 … 4 or 10 = Position of the Communication Module;14 = I/O-Bus; 31 = Module itself

The identifier is not contained in the CI501-PNIO diagnosis block.

2) With “Device” the following allocation applies: 31 = Module itself; 1..10 = Expansion module
3)

With “Modul” the following allocation applies:

31 = Module itself

Module type (1 = AI, 2 = DO, 3 = AO)

4) This message appears, if externally voltages at one or more terminals DO0..DO7 cause that other digital outputs are supplied through that voltage CI501-PNIO. All outputs of the apply digital output groups will be turned off for 5 seconds. The diagnosis message appears for the whole output group.
5) The voltage on digital outputs DO0..DO7 has overrun the process supply voltage UP3 CI501-PNIO. Diagnosis message appears for the whole module.
6) This message appears, if the output of a channel DO0..DO7 should be switched on while an externally voltage is connected. In this case the start up is disabled, as long as the externally voltage is connected. Otherwise this could produce reverse voltage from this output to other digital outputs. This diagnosis message appears per channel.
7) Short circuit: After a detected short circuit, the output is deactivated for 100ms. Then a new start up will be executed. This diagnosis message appears per channel.