Displays

Statuses of the LEDs:
LED Status Color LED = OFF LED = ON LED Flashes
PWR System voltage Green System firmware is not running System firmware is running –
CS31 A CS31 communication Green No communication at CS31 Bus A Communication at CS31 Bus A OK 10 Hz: Not bit lifetime management
C. B CS31 communication Green No communication at CS31 Bus B Communication at CS31 Bus B OK 10 Hz: Not bit lifetime management
S-ERR Sum Error Red – Internal error detected 2 Hz: Diagnostic event happened
I/O-Bus Communication via the I/O Bus Green No I/O Bus communication Expansion modules connected 2 Hz: Error I/O-Bus
RUN A CPU active Green CPU A is not primary CPU A is primary

RUN B LED off:

CI590-CS31-HA primary self selection. No primary order from both PLC. PLC A has been selected as primary.

RUN B LED on: 2 primary orders. PLC B is primary.

R. B CPU active Green CPU B is not primary CPU B is primary

RUN A LED off:

CI590-CS31-HA primary self selection. No primary order from both PLC. PLC B has been selected as primary.

RUN A LED on: 2 primary orders. PLC A is primary.

SYNC-ERR Outputs from CPU A and CPU B Red – Configuration conflict detected

10 Hz: Not parameterized

2 Hz: Switch-over has occured

C0 … C15 Digital inputs/outputs Yellow Input/output = OFF Input/output = ON (the input voltage is even displayed if the supply voltage is OFF) –
UP Process supply voltage and initialization Green Process voltage is missing

Process voltage

OK and initialization completed

Module was not initialized correctly
CH-ERR3   Red No error Severe error within the corresponding group Error on one channel of the corresponding group (e.g. short-circuit at an output)
CH-ERR4   Red No error Severe error within the corresponding group Error on one channel of the corresponding group (e.g. short-circuit at an output)
CH-ERR *) Module error Red No error or process voltage is missing Internal error –
*) All LEDs CH-ERR2 to CH-ERR4 light up together