Technical Data of the Analog Outputs

Parameter Value
Number of channels per module 4, all channels for voltage and current
Distribution of channels into groups 1 group of 4 channels
  Channels O0-…O3- Terminals 3.0…3.3
  Channels O0+…O3+ Terminals 4.0…4.3
Output type Bipolar with voltage, unipolar with current
Galvanic isolation Against internal supply and other modules
Configurability -10…+10 V, 0…20 mA, 4…20 mA (each output can be configured individually), current outputs only channels 0…3
Output resistance (load), as current output 0…500 W
Output loadability, as voltage output Max. ± 10 mA
Indication of the output signals One LED per channel
Output data length 8 bytes
Resolution 12 bits (+ sign)
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ.

± 0.5 % of full scale

at 25°C

Max.

± 1 % of full scale (all ranges)

at 0…60 °C or EMC disturbance

Relationship between output signal and hex code See table, Measuring Ranges
Unused outputs Can be left open-circuited