Technical \ Data of the Analog Inputs

Parameter Value
Number of channels per module 4
Distribution of channels into groups 1 group of 4 channels
Connections of the channels I0- to I3- Terminals 1.0 to 1.3
Connections of the channels I0+ to I3+ Terminals 2.0 to 2.3
Input type Bipolar (not with current or Pt100/Pt1000/Ni1000)
Galvanic isolation Against internal supply and other modules
Configurability 0…10 V, -10…+10 V, 0/4…20 mA, Pt100/1000, Ni1000 (each input can be configured individually)
Channel input resistance Voltage: > 100 kW, current: ca. 330 W
Time constant of the input filter Voltage: 100 µs, current: 100 µs
Indication of the input signals One LED per channel
Conversion cycle 2 ms (for 8 inputs + 8 outputs), with Pt/Ni… 1 s
Resolution

Range 0…10 V: 12 bits

Range -10…+10 V: 12 bits + sign

Range 0…20 mA: 12 bits

Range 4…20 mA: 12 bits

Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ.

± 0.5 % of full scale

at 25°C

Max.

± 1 % of full scale (all ranges)

at 0…60 °C or EMC disturbance

Relationship between input signal and hex code See tables, Measuring Ranges
Unused voltage inputs Are configured as “unused”
Unused current inputs Have a low resistance, can be left open-circuited
Input data length 8 bytes
Overvoltage protection Yes