Diagnosis

E1..E4 d1 d2 d3 d4

Identifier

000..063

AC500 display <− Display in
Class Comp Dev Mod Ch Err PS501 PLC Browser

Byte 6

Bit 6..7

- Byte 3 Byte 4 Byte 5

Byte 6

Bit 0..5

PNIO diagnosis block
Class Interface Device Module Channel Error Identifier Error message Remedy
  1) 2) 3) 4)      
Module error
3 14 1..10 31 31 19 Checksum error in the I/O module Replace I/O module
11 / 12 ADR 1..10
3 14 1..10 31 31 9 Overflow diagnosis buffer Restart
11 / 12 ADR 1..10
3 14 1..10 31 31 26 Parameter error Check master
11 / 12 ADR 1..10
3 14 1..10 31 31 11 Process voltage too low Check process voltage
11 / 12 ADR 1..10
Channel error
4 14 1..10 3 0…1 48 Analog value overflow at an analog output Check output value or terminal
11 / 12 ADR 1..10
4 14 1..10 3 0…1 7 Analog value underflow at an analog output Check output value
11 / 12 ADR 1..10

Remarks:

1)

In AC500 the following interface identifier applies:

14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2.

The PNIO diagnosis block does not contain this identifier.

2)

With “Device” the following allocation applies:

31 = module itself, 1..10 = expansion module 1..10, ADR = hardware address (e. g. of the DC551-CS31)

3)

With “Module” the following allocation applies depending on the master:

Module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1..10 = expansion 1..10

Channel error: I/O bus or PNIO = module type (3 = AO); COM1/COM2: 1..10 = expansion 1..10

4) In case of module errors, with channel “31 = Module itself” is output.