Status LEDs

The LEDs are located at the front of module. There are 2 different groups:

  • The 5 system LEDs (PWR, NET, DC, S-ERR and I/O-Bus) show the operation status of the module and display possible errors.
  • The 29 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process supply voltage and the statuses of the inputs and outputs and display possible errors.
Status of the 5 System LEDs
LED Color Off On Flashing 1x flash 2x flash
PWR/RUN Green Error in the internal supply voltage or process voltage missing Internal supply voltage OK Module is not configured – –
Yellow – – – – –
NET Green Init Operational Pre-operational Safe-operational –
Red No error PDI Watchdog Timeout Invalid Configuration Unsolicited State Change Application time out
DC *) Green Distributed Clock not active Distributed Clock active – – –
Red – – – – –
S-ERR Red No error Internal error – – –
I/O-Bus Green No expansion modules connected or communication error — — – –
ETH1 Green No ETHERCAT connection

Link OK

No data transfer

Link OK

Data transfer OK

– –
Yellow – – – – –
ETH2 Green No ETHERCAT connection

Link OK

No data transfer

Link OK

Data transfer OK

– –
Yellow – – – – –
*) The status of this LED is only significant if the camswitch functionality is enabled
Status of the 29 Process LEDs
LED Color OFF ON Flashing
DC0 to DC7 Yellow Input/Output is OFF Input/Output is ON –
DI8 to DI15 Yellow Input is OFF Input is ON (the input voltage is even displayed if the supply voltage is OFF) –
DO8 to DO15 Yellow Output is OFF Output is ON –
UP Green Process supply voltage missing Process supply voltage OK and initialization finished –
UP3 Green Process supply voltage missing Process supply voltage OK –
CH-ERR1 to CH-ERR3 Red No error or process supply voltage missing Internal error Error on one channel of the corresponding group