LED State Displays

../_images/c0880f86984196120a331390009bd0a2
LED Color State Description
PWR green ON (light) Power supply available.
OFF (dark) Power supply not available or defective hardware.
RDY yellow ON Boot procedure
Blinking Boot failure
OFF
RUN green ON Communication module is operational.
Blinking
OFF Communication module is not operational.
CAN-RUN green ON Operational: Device is in the OPERATIONAL state.
Single Flash Stopped: Device is in STOPPED state.
Blinking Pre-operational: Device is in the PREOPERATIONAL state.
OFF No communication or no power supply.
CAN-ERR red ON Bus Off: The CAN controller is bus off.
Single flash Warning limit reached: At least one of the error counters of the CAN controller has reached or exceeded the warning level (too many error frames).
Double flash Error control event: A guard event (NMT Slave or NMTmaster) or a heartbeat event (Heartbeat consumer) has occurred.
OFF No Error: Device is in working condition.