LED State Displays

../_images/c0880f86984196120a331390009bd0a2
LED Color State Description
PWR green ON (light) Power supply available.
OFF (dark) Power supply not available or defective hardware.
RDY yellow ON Boot procedure
Blinking Boot failure
OFF —
RUN green ON Communication module is operational.
Blinking —
OFF Communication module is not operational.
CAN-RUN green ON Operational: Device is in the OPERATIONAL state.
Single Flash Stopped: Device is in STOPPED state.
Blinking Pre-operational: Device is in the PREOPERATIONAL state.
OFF No communication or no power supply.
CAN-ERR red ON Bus Off: The CAN controller is bus off.
Single flash Warning limit reached: At least one of the error counters of the CAN controller has reached or exceeded the warning level (too many error frames).
Double flash Error control event: A guard event (NMT Slave or NMTmaster) or a heartbeat event (Heartbeat consumer) has occurred.
OFF No Error: Device is in working condition.