| Number of channels per module |
6 transistor outputs (24 V DC, 0.5 A max.) |
| Distribution of the channels into groups |
1 group of 6 channels |
| Galvanic isolation |
Yes, per group |
| Connection of the channels DO0 to DO5 |
Terminals 13 to 18 |
| Common power supply voltage |
Terminals 19 (+24 V DC, signal name UP) and 20 (0 V DC, signal name ZP) |
| Reference potential for the channels DO0 to DO5 |
Terminal 20 (minus pole of the process voltage, name ZP) |
| Indication of the output signals |
1 yellow LED per channel; the LED is on when the output signal is high (signal 1) |
| Way of operation |
Non-latching type |
| Min. output voltage at signal 1 |
20 V DC at max. current consumption |
| Output delay (max. at rated load) |
|
| 0 to 1 |
50 µs |
| 1 to 0 |
200 µs |
| Rated protection fuse (per group) |
3 A fast |
| Output current |
|
| Rated current per channel (max.) |
0.5 A at UP 24 V DC |
| Rated current per group (max.) |
3 A |
| Rated current (all channels together, max.) |
3 A |
| Lamp load (max.) |
5 W |
| Max. leakage current with signal 0 |
0.5 mA |
| Demagnetization when inductive loads are switched off |
Must be performed externally according to driven load specification |
| Switching Frequencies |
|
| With inductive loads |
Max. 0.5 Hz |
| With lamp loads |
Max. 1 Hz at max. 5 W |
| Short circuit / Overload proof |
No |
| Overload message |
No |
| Output current limitation |
No |
| Resistance to feedback against 24 V DC |
No |
| Connection of 2 outputs in parallel |
Not possible |
| Max. cable length |
|
| Shielded |
500 m |
| Unshielded |
150 m |