Connection of the Digital Transistor \ Outputs (PM55x-T(P) only)

../_images/5e018004e387dd5b0a33139000eba54e

Electrical connection of digital transistor outputs

Attention

:strong:Risk of malfunctions in the plant!

The outputs may switch on for a period of 10 to 50 µs if the process supply voltage UP/ZP is switched on.

This must be considered in the planning of the application.

Caution

:strong:Risk of damaging the processor module!

The outputs are not protected against short circuit and overload.

  • Never short-circuit or overload the outputs.
  • Never connect the outputs to other voltages.
  • Use an external 3 A fast protection fuse for the outputs.