Parameterization¶
Firmware version | Configuration |
---|---|
Firmware version > V2.0.0 | The arrangement of the parameter data is performed by Control Builder Plus/ Automation_Builder software. |
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
Module: Module slot address: Y = 1…10
Name | Value | Internal value | Internal value, type | Default | Min. | Max. | EDS Slot/Index |
---|---|---|---|---|---|---|---|
Module ID | Internal | 1220 1) |
Word | 1220 0x04C4 |
0 | 65535 | 0x0Y01 |
Ignore module 2) |
No Yes |
0 1 |
Byte | No 0x00 |
Not for FBP | ||
Parameter length | Internal | 7 | Byte | 7-CPU 6-FBP |
0 | 255 | 0x0Y02 |
Check supply | Off On |
0 1 |
Byte | On 0x01 |
0 | 1 | 0x0Y03 |
Input delay | 0.1 ms 1 ms 8 ms 32 ms |
0 1 2 3 |
Byte | 8 ms 0x02 |
0 | 3 | 0x0Y04 |
Fast counter 4) |
0 : 10 3) |
0 : 10 |
Byte | Mode 0 0x00 |
Not for FBP | ||
Short-circuit detection of output or sensor supply | Off On |
0 1 |
Byte | On 0x01 |
0 | 1 | 0x0Y05 |
Behaviour of outputs at communication errors | Off Last value Substitute value |
0 1+(n*5) 2+(n*5), n £ 2 |
Byte | Off 0x00 |
0 | 2 | 0x0Y06 |
Substitute value at outputs Bit 15 = Output 15 Bit 0 = Output 0 |
0… 65535 |
0… 0xffff |
Word | 0 0x0000 |
0 | 65535 | 0x0Y07 |
Remarks:
1) | With CS31 and addresses smaller than 70 and FBP, the value is increased by 1 |
2) | Not with FBP |
3) | For a description of the counter operating modes, please refer to the Fast Counter section Fast Counter |
4) | With FBP or CS31 without the parameter Fast counter |
GSD file:
Ext_User_Prm_Data_Len = Ext_User_Prm_Data_Const(0) = |
9 0x04, 0xc5, 0x06, \ 0x01, 0x02, 0x01, 0x00, 0x00, 0x00; |