Insulation Test Voltages, Routine Test

According to EN 61131-2

230 V circuits against other circuitry 2500 V 1.2/50 µs
120 V circuits against other circuitry 1500 V 1.2/50 µs
120 V to 240 V circuits against other circuitry 2500 V 1.2/50 µs
     
24 V circuits (supply, 24 V inputs/outputs, analogue inputs/outputs), if they are electrically isolated against other circuitry 500 V 1.2/50 µs
COM interfaces, electrically isolated 500 V 1.2/50 µs
COM interfaces, electrically not isolated Not applicable Not applicable
FBP interface 500 V 1.2/50 µs
Ethernet 500 V 1.2/50 µs
ARCNET 500 V 1.2/50 µs
     
230 V circuits against other circuitry 1350 V AC 2 s
120 V circuits against other circuitry 820 V AC 2 s
120 V to 240 V circuits against other circuitry 1350 V AC 2 s
     
24 V circuits (supply, 24 V inputs/outputs, analogue inputs/outputs), if they are electrically isolated against other circuitry 350 V AC 2 s
COM interfaces, electrically isolated 350 V AC 2 s
COM interfaces, electrically not isolated Not applicable Not applicable
FBP interface 350 V AC 2 s
Ethernet 350 V AC 2 s
ARCNET 350 V AC 2 s