Parameterization

The arrangement of the parameter data is performed with Automation_Builder software, versions ≥ 1.2.3.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module: Module slot address: Y = 1…7

Name Value Internal value Internal value, type Default Min. Max. Max.
Module ID Internal

1105

1)

WORD

1105

0x0451

0 65535 0x0Y01

Ignore module

2)

No

Yes

0

1

BYTE

No

0x00

    not for FBP
Parameter length Internal 6 BYTE

6-CPU

6-FBP

0 6 0x0Y02
Check supply

Off

on

0

1

BYTE

On

0x01

0 1 0x0Y03
Reserve 0 … 255 0 … 0xff BYTE

On

0x01

0 1 0x0Y04
Behaviour of outputs at communication errors

Off

Last value

Substitute value

0

1+(n*5)

2+(n*5),

n <= 2

BYTE

Off

0x00

0 2 0x0Y05

Substitute value at outputs

Bit 7 = Output 7

Bit 0 = Output 0

0…

255

0…

0xff

BYTE 0x00 0 255 0x0Y06
Reserve 0 … 255 0 … 0xff BYTE 0x00 0 255 0x0Y07
Reserve 0 … 255 0 … 0xff BYTE 0x00 0 255 0x0Y08

1) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1

2) Not with FBP

GSD file:

Ext_User_Prm_Data_Len = 10
Ext_User_Prm_Data_Const(0) = 0x04, 0x51, 0x00, 0x06, 0x01, 0x01, 0x00, 0x00, 0x00, 0x00