Parameterization¶
The arrangement of the parameter data is performed with Automation_Builder software, versions ≥ 1.2.3.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
Module: Module slot address: Y = 1…7
Name | Value | Internal value | Internal value, type | Default | Min. | Max. | Max. |
---|---|---|---|---|---|---|---|
Module ID | Internal | 1105 1) |
WORD | 1105 0x0451 |
0 | 65535 | 0x0Y01 |
Ignore module 2) |
No Yes |
0 1 |
BYTE | No 0x00 |
not for FBP | ||
Parameter length | Internal | 6 | BYTE | 6-CPU 6-FBP |
0 | 6 | 0x0Y02 |
Check supply | Off on |
0 1 |
BYTE | On 0x01 |
0 | 1 | 0x0Y03 |
Reserve | 0 … 255 | 0 … 0xff | BYTE | On 0x01 |
0 | 1 | 0x0Y04 |
Behaviour of outputs at communication errors | Off Last value Substitute value |
0 1+(n*5) 2+(n*5), n <= 2 |
BYTE | Off 0x00 |
0 | 2 | 0x0Y05 |
Substitute value at outputs Bit 7 = Output 7 Bit 0 = Output 0 |
0… 255 |
0… 0xff |
BYTE | 0x00 | 0 | 255 | 0x0Y06 |
Reserve | 0 … 255 | 0 … 0xff | BYTE | 0x00 | 0 | 255 | 0x0Y07 |
Reserve | 0 … 255 | 0 … 0xff | BYTE | 0x00 | 0 | 255 | 0x0Y08 |
1) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1 2) Not with FBP |
GSD file:
Ext_User_Prm_Data_Len = | 10 |
Ext_User_Prm_Data_Const(0) = | 0x04, 0x51, 0x00, 0x06, 0x01, 0x01, 0x00, 0x00, 0x00, 0x00 |