LED Status Display

The LEDs are located at the front of module. There are 2 different groups:

  • The 5 system LEDs (PWR, STA1 DP, STA2 DP, S-ERR and I/O-Bus) show the operation status of the module and display possible errors.
  • The 29 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process supply voltage and the statuses of the inputs and outputs and display possible errors.
Status of the 5 System-LEDs:
LED Color OFF ON Flashing
PWR/RUN Green Process supply voltage missing Internal supply voltage OK, module ready for communication with IO Controller Start-up / preparing communication
Yellow
STA1-DP Green PROFIBUS running Invalid device parameters
STA2-DP Red No error Bus timeout No communication to Master
S-ERR Red No error Internal error
I/O-Bus Green No expansion modules connected or communication error Expansion modules connected and operational
Status of the 29 process LEDs:
LED Color OFF ON Flashing
DC0 to DC7 Yellow Input/Output is OFF Input/Output is ON
DI8 to DI15 Yellow Input is OFF Input is ON (the input voltage is even displayed if the supply voltage is OFF)
DO8 to DO15 Yellow Output is OFF Output is ON
UP Green Process supply voltage missing Process supply voltage OK and initialization finished
UP3 Green Process supply voltage missing Process supply voltage OK
CH-ERR1 to CH-ERR3 Red No error or process supply voltage missing Internal error Error on one channel of the corresponding group