LED Status Display
The LEDs are located at the front of module. There are 2 different groups:
- The 5 system LEDs (PWR, STA1 DP, STA2 DP, S-ERR and I/O-Bus) show the operation status of the module and display possible errors.
- The 29 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process supply voltage and the statuses of the inputs and outputs and display possible errors.
Status of the 5 System-LEDs:
| LED |
Color |
OFF |
ON |
Flashing |
| PWR/RUN |
Green |
Process supply voltage missing |
Internal supply voltage OK, module ready for communication with IO Controller |
Start-up / preparing communication |
| Yellow |
— |
— |
— |
| STA1-DP |
Green |
— |
PROFIBUS running |
Invalid device parameters |
| STA2-DP |
Red |
No error |
Bus timeout |
No communication to Master |
| S-ERR |
Red |
No error |
Internal error |
– |
| I/O-Bus |
Green |
No expansion modules connected or communication error |
Expansion modules connected and operational |
— |
Status of the 29 process LEDs:
| LED |
Color |
OFF |
ON |
Flashing |
| DC0 to DC7 |
Yellow |
Input/Output is OFF |
Input/Output is ON |
– |
| DI8 to DI15 |
Yellow |
Input is OFF |
Input is ON (the input voltage is even displayed if the supply voltage is OFF) |
– |
| DO8 to DO15 |
Yellow |
Output is OFF |
Output is ON |
– |
| UP |
Green |
Process supply voltage missing |
Process supply voltage OK and initialization finished |
– |
| UP3 |
Green |
Process supply voltage missing |
Process supply voltage OK |
– |
| CH-ERR1 to CH-ERR3 |
Red |
No error or process supply voltage missing |
Internal error |
Error on one channel of the corresponding group |