Mounting and Demounting of S500-eCo I/O Modules¶
S500-eCo I/O-modules can be mounted either on a DIN rail or with screws on a metal plate.
Mounting I/O Modules on a DIN Rail
Attention
:strong:Risk of function faults!
The S500-eCo I/O modules are earthed via the DIN rail.
The DIN rail must be included into the earthing concept of the plant.
Use only metal screws.
Mount I/O module at the top of the DIN rail, then snap it in below.
- ⇒
Attach I/O module by hand to an other module. The serial I/O bus is connected automatically.
- ⇒
Demounting I/O Modules Mounted \ on a DIN Rail
Remove I/O module by hand if connected.
- ⇒
While pressing down I/O module pull it away from DIN rail.
- ⇒
Mounting I/O Modules on a Metal Plate
Attention
:strong:Risk of function faults!
Missing electrical contact by isolating screws or washers!
Use metal screws on the metal plate.
The metal plate must be included into the earthing concept of the plant.
Do NOT use isolating washers!
Note
One TA566 wall mounting accessory TA566 - Wall Mounting Accessory is needed per S500-eCo I/O module.
Snap in the TA566 at the back side of the I/O module.
- ⇒
Attach the I/O module by hand to an other module. The serial I/O bus is connected automatically.
- ⇒
Fasten the I/O module with two screws (max. diameter: 4 mm) to the metal plate.
- ⇒
Demounting I/O Modules Mounted \ on a Metal Plate
Remove the 2 screws.
- ⇒
Remove the I/O module from the connected module by hand.
- ⇒