Technical data of the digital inputs/outputs if used as inputs¶
Parameter | Value | |
---|---|---|
Number of channels per module | Max. 24 digital inputs | |
Reference potential for all inputs | Terminals 1.9, 2.9, 3.9 and 4.9 (minus pole of the process supply voltage, signal name ZP) | |
Galvanic isolation | From the rest of the module | |
Indication of the input signals | 1 yellow LED per channel, the LED is ON when the input signal is high (signal 1) | |
Input type acc. to EN 61131-2 | Type 1 | |
Input delay (0->1 or 1->0) | Typ. 8 ms, configurable from 0.1 to 32 ms | |
Input signal voltage | 24 V DC | |
Signal 0 | -3 V…+5 V * | |
Undefined signal | > +5 V…< +15 V | |
Signal 1 | +15 V…+30 V | |
Ripple with signal 0 | Within -3 V…+5 V * | |
Ripple with signal 1 | Within +15 V…+30 V | |
Input current per channel | ||
Input voltage +24 V | Typ. 5 mA | |
Input voltage +5 V | > 1 mA | |
Input voltage +15 V | > 5 mA | |
Input voltage +30 V | < 8 mA | |
Max. cable length | ||
Shielded | 1000 m | |
Unshielded | 600 m |
* Due to the direct connection to the output, the demagnetizing varistor is also effective at the input (see figure) above. This is why the difference between UPx and the input signal must not exceed the clamp voltage of the varistor. The varistor limits the clamp voltage to approx. 36 V. Consequently, the input voltage must range from - 12 V to + 30 V when UPx = 24 V and from - 6 V to + 30 V when UPx = 30 V.