FunctionalityΒΆ

Interface ETHERNET
Protocol PROFINET IO RT
Power supply From the process supply voltage UP
Supply of the electronic circuitry of the I/O expansion modules attached Through the expansion bus interface (I/O-Bus)
Rotary switches For setting the IO Device identifier for configuration purposes (00h to FFh)
Configurable digital inputs/outputs 8 (configurable via software)
Digital inputs 8 (24 VDC; delay time configurable via software)
Digital outputs 8 (24 VDC, 0.5 A max.)
LED displays For system displays, signal statuses, errors and power supply
External supply voltage Via terminals ZP, UP and UP3 (process supply voltage 24 VDC)
Effect of incorrect input terminal connection Wrong or no signal detected, no damage up to 35 V
Required Terminal Unit TU507 or TU508 TU507-ETH and TU508-ETH for ETHERNET Communication Interface Modules