Technical Data of the Module

Parameter Value
Rated supply voltage of the module 24 V DC (UP/ZP)
Current consumption of the module (UP) 15 mA
Process voltage UP  
  Rated value 24 VDC (for inputs and outputs)
  Max. current loadability for the supply terminals 10 A
  Protection against reversed voltage Yes
  Rated protection fuse at UP 10 A fast
  Electrical isolation CS31 bus interface from the rest of the module
  Inrush current from UP (at power-up) 0.040 A²s
  Current consumption from UP at normal operation / with outputs 0.1 A + max. 0.008 A per input + max. 0.5 A per output
  Connections Terminals 1.8 - 4.8 for +24 V (UP) and 1.9 - 4.9 for 0 V (ZP)
Max. power dissipation within the module 6 W (outputs unloaded)
Number of digital inputs 8
Number of configurable digital inputs/outputs 16
Reference potential for all digital inputs and outputs Minus pole of the supply voltage, signal name ZP
Address setting With 2 rotary switches on the front panel
Diagnosis Diagnosis and Displays DC551-CS31 - Digital Inputs and Output
Operating and error displays 32 LEDs altogether
Weight (without terminal unit) Ca. 125 g
Mounting position

Horizontal

Or vertical with derating (output load reduced to 50 % at 40°C per group)

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.

No effects of multiple overloads