Connection of Resistance Thermometers in 2-wire Configuration to the \ Analog Inputs¶
When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow to build the necessary voltage drop for the evaluation. For this, the module CI592-CS31 provides a constant current source which is multiplexed over the max. 4 analog input channels.
The following figure shows the connection of resistance thermometers in 2-wire configuration to the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
Connection of resistance thermometers in 2-wire configuration to the analog inputs
Pt100 | -50 °C…+400 °C | 2-wire configuration, 1 channel used |
Pt1000 | -50 °C…+400 °C | 2-wire configuration, 1 channel used |
Ni1000 | -50 °C…+150 °C | 2-wire configuration, 1 channel used |
The measuring ranges are described in the section Measuring Ranges CI592-CS31 - Digital and Analog Inputs and Outputs CI592-CS31 - Digital and Analog Inputs and Outputs:
The module CI592-CS31 performs a linearization of the resistance characteristic.
Configure unused analog input channels as “unused”.