Technical Data of the Digital Inputs

Parameter Value
Number of channels per module 16 AC inputs (100-240 V AC)
Distribution of the channels into groups 2 (8 channels per group)
Input voltage range 0 ..264 V AC (47…63 Hz)
Input current per channel (typically at 25 °C)

< 3 mA (at 40 V AC)

> 6 mA (at 164 V AC)

> 8 mA (at 240 V AC)

Connections of the channels I0..I7 Terminals 1…8
Connections of the channels I8..I15 Terminals 10…17
Reference potential for the channels I0..I7 Terminal 9
Reference potential for the channels I8..I15 Terminal 18
Indication of the input signals 1 yellow LED per channel. The LED is on when the input signal is high (signal 1).
Input type according to EN 61131-2 Type 1
Input signal range  
  Signal 0 (max.) 40 V AC
  Undefined signal 40 V AC < U < 79 V AC
  Signal 1 (min.) 79 V AC
Input delay  
  signal 0 -> 1 Typ. 24 ms
  signal 1 -> 0 Typ. 24 ms
Input data length 2 bytes
Max. permissible leakage current (at 2-wire proximity switches) 1 mA
Max. cable length  
  Shielded 1000 m
  Unshielded 600 m