Technical Data of the Analog Outputs¶
| Parameter | Value | ||
|---|---|---|---|
| Number of channels per module | 2 configurable voltage or current outputs | ||
| Distribution of channels into groups | 1 (2 channels per group) | ||
| Connection of the signals O0U- and O1U+ | Terminals 13 and 15 | ||
| Connection of the signals O0I+ and O1I+ | Terminals 14 and 16 | ||
| Output type | Bipolar with voltage, unipolar with current | ||
| Resolution | 12 bits or 11 bits plus sign | ||
| Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range | Typ. | ± 0.5 % of full scale at 25 °C |
|
| Max. | ± 2 % of full scale at 0 °C … +60 °C or EMC disturbances |
||
| Indication of the output signals | No | ||
| Output Resistance (load) as current output | 0 … 500 W | ||
| Output load ability as voltage output | ± 2 mA max. | ||
| Output data length | 4 bytes | ||
| Relationship between output signal and hex code | Table AO561 - Analog Output Module | ||
| Unused outputs | Must not be connected and must be configured as “unused” | ||
| Overvoltage protection | Yes, up to 30 V DC | ||
| Max. cable length (conductor cross section > 0,14 mm²) | |||
| Unshielded wire | 10 m | ||
| Shielded wire | 100 m | ||