| Number of channels per module |
16 transistor outputs (24 V DC, 0.5 A max.) |
| Distribution of the channels into groups |
1 (16 channels per group) |
| Connection of the channels O0 to O7 |
Terminals 1 to 9 |
| Connection of the channels O8 to O15 |
Terminals 11 to 18 |
| Common power supply voltage |
Terminal 19 (positive pole of the process voltage, signal name UP) |
| Reference potential for the channels O0 to O15 |
Terminal 20 (negative pole of the process voltage, signal name ZP) |
| Indication of the output signals |
1 yellow LED per channel; the LED is on when the output signal is high (signal 1) and the module is powered via the I/O bus |
| Way of operation |
Non-latching type |
| Min. output voltage at signal 1 |
UP -0.3 V at max. current consumption |
| Output delay (max. at rated load) |
|
| |
0 to 1 |
50 µs |
| |
1 to 0 |
200 µs |
| Output data length |
2 bytes |
| Output current |
|
| |
Rated current per channel (max.) |
0.5 A at UP 24 V DC |
| |
Rated current per group (max.) |
8 A |
| |
Lamp load (max.) |
5 W |
| Max. leakage current with signal 0 |
0.5 mA |
| Output type |
Non-protected |
| Protection type |
External fuse on each channel |
| Rated protection fuse (for each channel) |
3 A fast |
| Demagnetization when inductive loads are switched off |
Must be performed externally according to driven load specification |
| Switching Frequencies |
|
| |
With inductive loads |
Max. 0.5 Hz |
| |
With lamp loads |
Max. 11 Hz at max. 5 W |
| Short circuit / Overload proof |
No |
| |
Overload message |
No |
| |
Output current limitation |
No |
| |
Resistance to feedback against 24 V DC |
No |
| Connection of 2 outputs in parallel |
Not possible |
| Max. cable length |
|
| |
Shielded |
500 m |
| |
Unshielded |
150 m |