General Principles¶
General Considerations
Electric and electronical devices have to work correctly on site. This is also valid when electro-magnetic influences affect them in defined and/or expected strength. The devices themselves must not emit electro-magnetic noises.
Advant Controller components have a very high noise immunity.
When the wiring and earthing instructions are met, an error-free operation is given.
High electro-magnetic noises of nearby mounted applications must be taken in consideration during the planning phase.
An EMC compatible earthing concept will also guarantee an error-free operation here.
Note
:strong:There are three important principles to be especially considered:
- Keep all connections as short as possible (in particular the earthing conductors)
- Use large conductor cross sections (in particular for the earthing conductors)
- Create low-impedance, i.e. good and large-sized contacts (in particular for the earthing conductors)
Note
:strong:Pay attention to the following:
- Use vibration-resistant connections
- Clean metallic contact areas
- Use solid plug and screw-type connections
- Use earth cable shields with clips on a well-grounded metallic surface
- Do not use aluminium parts
- Do not use sheath wires
- Do not use toothed lock washers under screw connections
Assembly: wrong
Assembly: correct
Make a connection between the DIN rails and PE (Protective Earth). For this, use an earthing wire with a minimum conductor cross section of 10 mm².
The wire is connected to the DIN rail with an M6 screw.
A large-area contact of the DIN rail with the metallic mounting plate improves the EMC behaviour significantly, as the disturbances can be discharged more effective.