Environmental Conditions¶
Parameter | Value | |
---|---|---|
24 V DC | ||
Voltage | 24 V (-15 %, +20 %) | |
Protection against reverse polarity | Yes | |
120…240 V AC wide range supply | ||
Voltage | 120…240 V (-15 %, +10 %) | |
Frequency | 50/60 Hz (-6 %, +4 %) | |
Allowed interruptions of power supply | ||
DC supply | Interruption < 10 ms, time between 2 interruptions > 1 s, PS2 |
Attention
Exceeding the maximum process or supply voltage (< -35 V DC and > + 35 V DC) could lead to unrecoverable damage of the system.
Attention
For the supply of the modules, power supply units according to PELV or SELV specifications must be used.
Note
The creepage distances and clearances meet the requirements of the overvoltage category II, pollution degree 2.
Parameter | Value | |
---|---|---|
Temperature | ||
Operating | -40 °C … +70 °C -40 °C … -30 °C: Proper start-up of system; technical data not guaranteed -40 °C … 0 °C: Due to the LCD technology, the display might respond very slowly. -40 °C…+40 °C: Vertical mounting of modules possible, output load limited to 50 % per group +60 °C …+70 °C with the following deratings:
|
|
Storage / Transport | -40 °C … +85 °C | |
Humidity | Operating / Storage: 100 % r. H. with condensation | |
Air pressure | Operating: -1000 m …. 4000 m (1080 hPa … 620 hPa)
|
|
Immunity to corrosive gases | Operating: Yes, according to: ISA S71.04.1985 Harsh group A, G3/GX IEC 60721-3-3 3C2 / 3C3 |
|
Immunity to salt mist | Operating: Yes, horizontal mounting only, according to IEC 60068-2-52 severity level: 1 |
Attention
:strong:Risk of corrosion!
Unused connectors and slots may corrode if XC devices are used in salt-mist environments.
Protect unused connectors and slots with TA535 protective caps for XC devices TA535: Protective Caps TA535 for XC Devices TA535 - Protective Caps for XC Devices.
Parameter | Value |
---|---|
Radiated emission (radio disturbances) | Yes, according to: CISPR 16-2-3 |
Conducted emission (radio disturbances) | Yes, according to: CISPR 16-2-1, CISPR 16-1-2 |
Electrostatic discharge (ESD) | Yes, according to: IEC 61000-4-2, zone B, criterion B |
Fast transient interference voltages (burst) | Yes, according to: IEC 61000-4-4, zone B, criterion B |
High energy transient interference voltages (surge) | Yes, according to: IEC 61000-4-5, zone B, criterion B |
Influence of radiated disturbances | Yes, according to: IEC 61000-4-3, zone B, criterion A |
Influence of line-conducted interferences | Yes, according to: IEC 61000-4-6, zone B, criterion A |
Influence of power frequency magnetic fields | Yes, according to: IEC 61000-4-8, zone B, criterion A |
Note
In order to prevent malfunctions, it is recommended, that the operating personnel discharge themselves prior to touching communication connectors or perform other suitable measures to reduce effects of electrostatic discharges.
Attention
:strong:Risk of malfunctions!
Unused slots for communication modules are not protected against accidental physical contact.
- Unused slots for communication modules must be covered with dummy communication modules (TA524 TA524 - Dummy Communication Module to achieve IP20 rating.
- I/O bus connectors must not be touched during operation.