Environmental Tests

Parameter Value
Storage

IEC 60068-2-1 Test Ab: cold withstand test -40 °C / 16 h

IEC 60068-2-2 Test Bb: dry heat withstand test +85 °C / 16 h

Humidity

IEC 60068-2-30 Test Db: Cyclic (12 h / 12 h) Damp-Heat Test 55 °C, 93 % r. H. / 25 °C, 95 % r. H., 6 cycles

IEC 60068-2-78, Stationary Humidity Test: 40 °C, 93 % r. H., 240 h

Insulation Test IEC 61131-2
Vibration resistance

IEC 61131-2 / IEC 60068-26: 5 Hz … 500 Hz, 2 g (with SD Memory Card inserted)

IEC 60068-2-64: 5 Hz … 500 Hz, 4 g rms

Shock resistance IEC 60068-2-27: all 3 axes 15 g, 11 ms, half-sinusoidal
EMC Immunity
Parameter Value
Electrostatic discharge (ESD)

Electrostatic voltage in case of air discharge: 8 kV

Electrostatic voltage in case of contact discharge: 6 kV

Fast transient interference voltages (burst)

Supply voltage units (DC): 4 kV

Digital inputs/outputs (24 V DC): 2 kV

Analog inputs/outputs: 2 kV

Communication lines shielded: 2 kV

I/O supply (DC-out): 2 kV

High energy transient interference voltages (surge)

Supply voltage units (DC): 1 kV CM* / 0.5 kV DM*

Digital inputs/outputs (24 V DC): 1 kV CM* / 0.5 kV DM*

Analog inputs/outputs: 1 kV CM* / 0.5 kV DM*

Communication lines shielded: 1 kV CM*

I/O supply (DC-out): 0,5 kV CM* / 0.5 kV DM*

* CM = Common Mode, * DM = Differential Mode

Influence of radiated disturbances Test field strength: 10 V/m
Influence of line-conducted interferences Test voltage: 10 V
Power frequency magnetic fields

30 A/m 50 Hz

30 A/m 60 Hz