Diagnosis¶
E1..E4 | d1 | d2 | d3 | d4 | Identifier 000..063 |
AC500-Display | <− Display in | |
---|---|---|---|---|---|---|---|---|
Class | Comp | Dev | Mod | Ch | Err | PS501 PLC Browser | ||
Class | Inter- face |
Device | Module | Channel | Error- Identifier |
Error message | Remedy | |
Errors for Onboard I/O | ||||||||
Light errors | ||||||||
3 | 8 | 255 | 2 | 0 | 3 | MaxWaitRun for onboard I/O module has expired, when PLC is put into RUN state | Reboot and try it again. If the error still exists, replace processor module for testing | |
3 | 8 | 255 | 3 | 0 | 26 | Invalid configuration of onboard I/O module, e. g. 2 input channels are configured as fast counter and interrupt input at the same time. | Correct PLC configuration | |
Warnings | ||||||||
4 | 8 | 1 | 2 | 1 | 2 | Invalid configuration value for PWM channel. Frequency / cycletime for the PWM channel of the 8DI+6DO and 8DI+6DO+2AI+1AO module are common and if both channel are configured for PWM, the frequency of the second channel must be set to 0. | Correct frequency | |
4 | 8 | 1 | 2 | 0..1 | 4 | PWM channel frequency or cycle time too high | Correct frequency or cycle time | |
4 | 8 | 1 | 2 | 0..1 | 7 | PWM channel frequency or cycle time too low | Correct frequency or cycle time | |
4 | 8 | 1 | 2 | 0 | 52 | Frequency on interrupt input pin too high and interrupt events are missed | Correct frequency | |
4 | 8 | 4 | 2 | 0..1 | 48 | Analog input value too high | Correct value | |
4 | 8 | 5 | 2 | 0 | 48 | Analog output value too high | Correct value | |
4 | 8 | 255 | 2 | 0 | 26 | PLC was put into RUN state, although a configuration error is present, because parameter Run on config fault is set to YES | Correct PLC configuration | |
4 | 8 | 255 | 0 | 0 | 43 | Unspecified or internal error occured | Replace processor module |